CAJ 8014 - Miltiple, pipes (insul), cable, tray CP672 — page 787

Page text

Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
cUL
2 of 3
-
cUL SYSTEM NO. C-AJ-8014
MULTIPLE PENETRANTS THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL
CANADA ONLY
F-RATING = 2-HR.
FT-RATING = 0-HR., 1/4-HR., 1/2-HR., OR 1-HR.
FH AND FTH-RATINGS = 0-HR.
3. [OPTIONAL] ANY OR ALL STEEL OR IRON PIPES (8" OR SMALLER) OR COPPER PIPES (2" AND SMALLER)
MAY BE INSTALLED WITH MAXIMUM 1-1/2" THICK GLASS-FIBER PIPE INSULATION.
4. [NOT SHOWN] METAL JACKET INSTALLED ON ALL INSULATED COPPER PIPES. MINIMUM 6" LONG
JACKET OF MINIMUM 0.013" THICK STEEL SHEET METAL HAVING A MINIMUM 2" OVERLAP AT
LONGITUDINAL SEAM AND SECURED USING MINIMUM 1/2" WIDE STAINLESS STEEL HOSE CLAMP AT
CENTER OF JACKET. THE BOTTOM EDGE OF JACKET TO EXTEND MINIMUM 1" BELOW TOP SURFACE AT
FLOOR ASSEMBLY AND MINIMUM 5" ABOVE TOP SURFACE OF FLOOR ASSEMBLY.
5. MAXIMUM 3" NOMINAL DIAMETER CABLE BUNDLE TO CONSIST OF ANY OF THE FOLLOWING :
A. MAXIMUM 500 KCMIL SINGLE COPPER OR ALUMINUM CONDUCTOR POWER CABLE WITH PVC
JACKET.
B. MAXIMUM 300 PAIR NO. 24 AWG TELEPHONE CABLE WITH PVC JACKET.
C. MAXIMUM 7/C NO. 12 AWG POWER CABLE WITH PVC JACKET.
D. MAXIMUM 1/2" DIAMETER FIBER OPTIC CABLE WITH PVC JACKET.
E. MAXIMUM 3/C NO. 12 AWG STEEL CLAD CABLE.
6. MAXIMUM 4/C NO. 500 KCMIL ALUMINUM OR COPPER CONDUCTOR CLADDED CABLE.
7. MAXIMUM 4" NOMINAL DIAMETER EMT SLEEVE EXTENDING MINIMUM 10" TO MAXIMUM 12" BEYOND
BOTH SURFACE OF FLOOR OR WALL, WITH MAXIMUM 3" CABLE BUNDLE (ITEM NO. 5), AND TO BE
RIGIDLY SUPPORTED ON TOP SIDE OF FLOOR OR BOTH SIDES OF WALL ASSEMBLY.
8. MAXIMUM 24" x 4" ALUMINUM OR STEEL OPEN LADDER CABLE TRAY (MAX. QTY. = 1).
9. ANY COMBINATION OF THE FOLLOWING CABLES MAY BE USED WITHIN CABLE TRAYS :
A. MAXIMUM 300 PAIR NO. 24 AWG TELEPHONE CABLE.
B. MAXIMUM 3/C NO. 12 AWG METAL CLAD CABLE.
C. MAXIMUM 3/C (+GROUND) NO. 2 AWG METAL CLAD TEK CABLE WITH PVC OR PE JACKET.
10. HILTI CFS-PL FIRESTOP PLUG OR HILTI CP 658T FIRESTOP PLUG CUT TO FIT AROUND CABLE BUNDLE
AND INSTALLED TIGHTLY WITHIN SLEEVE (ITEM NO. 7) SUCH THAT THE OUTER CIRCUMFERENCE OF THE
DOME SHAPED PLUG IS FLUSH WITH THE BOTTOM SURFACE OF SLEEVE IN FLOORS, OR BOTH
SURFACES IN WALLS (SEE NOTE NO. 3 BELOW).
11. MINIMUM 2" THICKNESS MINERAL WOOL (MIN. 4 PCF DENSITY) TIGHTLY PACKED AND RECESSED TO
ACCOMMODATE SEALANT, FLUSH WITH TOP SURFACE OF SLEEVE (ITEM NO. 7) WITHIN FLOORS, OR
BOTH SURFACES IN WALLS.
12. MINIMUM 1/2" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT FLUSH WITH TOP OF SLEEVE IN
FLOOR ASSEMBLY OR BOTH SIDES OF WALL ASSEMBLY.
13. MINIMUM 4" THICKNESS MINERAL WOOL (MIN. 4 PCF DENSITY) TIGHTLY PACKED FLUSH WITH TOP
SURFACE OF FLOOR, OR BOTH SURFACES OF WALL.
14. MINIMUM 1/8" (WET) THICKNESS HILTI CFS-SP WB FIRESTOP JOINT SPRAY OR HILTI CP 672 SPEED
SPRAY TO COMPLETELY COVER MINERAL WOOL AND OVERLAP MINIMUM 1/2" ONTO PENETRATING
ITEMS AND CONCRETE FLOOR.
Mar. 12, 2012
cUL CAJ8014c.031212