Page text
Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
cUL
1 of 3
5/64" = 1"
Mar. 12, 2012
cUL SYSTEM NO. C-AJ-8014
cUL CAJ8014c.031212
MULTIPLE PENETRANTS THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL
CANADA ONLY
F-RATING = 2-HR.
FT-RATING = 0-HR., 1/4-HR., 1/2-HR., OR 1-HR.
FH AND FTH-RATINGS = 0-HR.
A
SECTION A-A
TOP VIEW
1. CONCRETE FLOOR OR WALL ASSEMBLY (2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR (MINIMUM 4-1/2" THICK).
B. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
2. ONE OR MORE OF THE FOLLOWING PENETRATING ITEMS (ITEMS 2-7) MAY BE INSTALLED WITHIN
OPENING AND IN ANY COMBINATION :
A. MAXIMUM 24" NOMINAL DIAMETER STEEL PIPE.
B. MAXIMUM 24" NOMINAL DIAMETER CAST OR DUCTILE IRON PIPE.
C. MAXIMUM 6" NOMINAL DIAMETER COPPER PIPE OR TUBING.
D. MAXIMUM 6" NOMINAL DIAMETER STEEL CONDUIT.
E. MAXIMUM 4" NOMINAL DIAMETER EMT.
F. MAXIMUM 2" NOMINAL DIAMETER FLEXIBLE STEEL CONDUIT.
A
1
3
5
6
7
8
9
101211
13
14
2
2