Page text
Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
cUL
3 of 3
-
cUL SYSTEM NO. C-AJ-8014
MULTIPLE PENETRANTS THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL
CANADA ONLY
F-RATING = 2-HR.
FT-RATING = 0-HR., 1/4-HR., 1/2-HR., OR 1-HR.
FH AND FTH-RATINGS = 0-HR.
NOTES : 1. MAXIMUM AREA OF OPENING IS 1024 SQ. IN. WITH A MAXIMUM DIMENSION OF 32".
2. CABLES TO FILL A MAXIMUM 45% CROSS-SECTIONAL AREA OF CABLE TRAY AND/OR
A MAXIMUM 3" LOADING DEPTH.
3. WHEN HILTI CFS-PL FIRESTOP PLUG OR HILTI CP 658T FIRESTOP PLUG IS USED
WITHIN SLEEVES, SLEEVE IS TO EXTEND A NOMINAL 10" BEYOND BOTTOM SURFACE
OF FLOOR OR BOTH SURFACES OF WALL.
4. HILTI CP 672 SPEED SPRAY IS REQUIRED ON BOTH SIDES OF A WALL ASSEMBLY.
ANNULAR SPACE
MINIMUMMAXIMUM
BETWEEN METALLIC PENETRANTS (2" AND SMALLER)
0"
13"
BETWEEN METALLIC PENETRANTS (GREATER THAN 2")
3"
13"
BETWEEN METALLIC PENETRANTS AND PERIPHERY OF OPENING
0"
13"
BETWEEN CABLE BUNDLES
3"
13"
BETWEEN CABLE BUNDLES AND OTHER PENETRANTS
3"
13"
BETWEEN CABLE BUNDLES AND PERIPHERY OF OPENING
1"
13"
AROUND CABLE BUNDLE WITHIN SLEEVE
1/2"
3/4"
BETWEEN INDIVIDUAL CABLES AND BETWEEN INDIVIDUAL CABLES AND OTHER
PENETRANTS
3"
13"
BETWEEN INDIVIDUAL CABLES AND PERIPHERY OF OPENING
1"
13"
BETWEEN CABLE TRAY AND CABLE BUNDLES
3"
13"
BETWEEN CABLE TRAY AND SLEEVE (METAL JACKET) INSULATED PENETRANTS
1"
13"
BETWEEN CABLE TRAY AND INSULATED PENETRANTS
5"
13"
BETWEEN CABLE TRAY AND PERIPHERY OF OPENING
1-1/2"
13"
BETWEEN INSULATED PENETRANTS
3"
13"
BETWEEN INSULATED PENETRANTS AND PERIPHERY OF OPENING
4"
13"
BETWEEN INSULATED PENETRANTS WITH METAL JACKET
3"
13"
BETWEEN INSULATED PENETRANTS WITH METAL JACKET AND PERIPHERY OF
OPENING
1/2"
13"
BETWEEN EMT SLEEVES
3/4"
13"
BETWEEN EMT SLEEVE AND OTHER PENETRANTS
2"
13"
BETWEEN EMT SLEEVE AND PERIPHERY OF OPENING
1/2"
13"
Mar. 12, 2012
cUL CAJ8014c.031212