Page text
Hilti (Canada) Corp. 1-800-363-4458 • www.hilti.ca • Hilti Firestop Systems Guide • 05/2011 Hilti. Outperform. Outlast. Hilti Firestop Saving lives through innovation and education Estimating Tables How to estimate amount of Firestop needed for pipe penetrations Single pipe, circular opening Single pipe, rectangular opening For multiple pipes in an opening Use the Estimation Chart (Table 3) found on page 387 Find the pipe size across the top of the table and match it with the hole diameter found along the side of the chart. The value from the table represents the volume of annular space to be filled per penetration at 1/2" depth of firestop. 1. Calculate the area of the pipe. For schedule 40 steel pipe, use the Calculation Chart For Pipe Areas (Table 1) found on page 387. Find the pipe size that is used and note the Area located in the far right column OR calculate the total cross- sectional area of the penetration using the following formula (note: all values should be in units of inches): $3 U3 [ $3 = total area of penetrating pipe U3 = outside radius of penetrating pipe = diameter BBBBBBBB Calculate the area of the opening (all values in units of inches): $R = length x width $R = area of opening Subtract the area of the penetrating pipe from the area of the opening and multiply by the depth of the firestop required: Total firestop required = (AR$3[)' )' = firestop depth Total annular space to be filled per penetration. For wall systems requiring firestopping on both sides, multiply by 2. Use the methods stated previously, but add all of the penetration areas (AS) together before subtracting from the total area of the opening (AR 6DPSOH3UREOHP APPLICATION: 3-hour fire rated concrete floor. Opening size is 8" dia. with nominal 6" dia. steel pipe. Use UL System C-AJ-1226 (1/4" depth FS-ONE) $R = 8" diameter 50.24 in $3 = 6" diameter - =34.19 in BBBBBBBB 16.05 in x 1/4" = 4.0 inRI)621(