CEJ 261P - (L) Speed Spray (1/8") 2 Hr - 8" max — page 1172

Page text

Division 07 – Thermal and Moisture Protection
OPL Design No. CEJ 261P
07 84 00 Fire stopping
07 84 53 Building Perimeter Fire stopping
Page 1 of 4
Date Revised: June 20, 2014
©Intertek
Project No: 100141291SAT-007
Design Number HI/PHV 120-07
PERIMETER FIRE BARRIER SYSTEM
Hilti, Inc.
ASTM E 2307
Table 1
Firestop
Joint Spray
CFS-SP WB
Silicone
Joint Spray
CFS-SP SIL
F-Rating
2 hr
2 hr
T-Rating
1 hr
1 hr
Application
Thickness
1/8" wet film
(1/16" dry)
2mm (0.079")
wet film
Cycling (%)
Horizontal
Vertical
See Note 1
± 7.5
± 5
± 7.5
± 5
L-Rating <1.0 SCFM/LF
1.  CONCRETE FLOOR ASSEMBLY: Two-
our rated concrete floor assembly made
from either lightweight or normal weight
concrete with a density of 100-150 pcf,
with a min. thickness of 4 in. at the joint
face. Overall slab thickness may vary to
accommodate various blockout depths
(longitudinal recesses) formed in the
concrete, to house the architectural