Page text
Sheet
Drawing No.
HILTI, Inc.
Date
Scale
WJ
POMM~
3 of 3
-
Jan. 28, 2013
UL/cUL SYSTEM NO. W-J-3200
F-RATING = 2-HR.
T-RATING = 1/4-HR.
L-RATING = SEE TABLE BELOW
tgPOMM~KMNOUNP
MULTIPLE CABLE BUNDLES THROUGH CONCRETE OR BLOCK WALL ASSEMBLY
Tulsa, Oklahoma USA (800) 879-8000
CFM PER CFS-SL GP FIRESTOP GANGPLATE AT AMBIENT AND 400° F
TYPE AND NUMBER OF DEVICES IN CFS-SL GP
(CAP - ITEM 4; DEVICES - ANY COMBINATION OF ITEMS 3A THROUGH 3C EXCEPT AS NOTED)
CAP(S) ONLY
CAP(S) AND
ONE DEVICE
CAP(S) AND
TWO DEVICES
CAP (OPT) AND
THREE DEVICES
FOUR
DEVICES
BLANK OPENING (NO CABLES) :
LESS THAN 1
1
2
2.5
3.5
OPENINGS WITH ANY
COMBINATION OF ITEM 5
CABLES FOR MAX 33%
AGGREGATE FILL IN DEVICE
TYPES 3B AND 3C, AND/OR MAX
100% VISUAL CABLE FILL IN
DEVICE TYPE 3A
-
2
4
6
8
CAP(S) ONLY
CAP(S) AND ONE
CP 653 DEVICE
(ITEM 3A)
CAP(S) AND TWO
CP 653 DEVICES
(ITEM 3A)
CAP (OPT) AND
THREE CP 653
DEVICES (ITEM 3A)
FOUR CP 653
DEVICES
(ITEM 3A)
OPENINGS WITH MAX 100%
VISUAL CABLE FILL WITH
CABLE TYPE 5D ONLY AND
CP 653 ONLY
-
1.5
3
4
5.5
CFM / SQ FT OF OPENING AT AMBIENT AND 400° F
TYPE AND NUMBER OF DEVICES IN CFS-SL GP
(CAP - ITEM 4; DEVICES - ANY COMBINATION OF ITEMS 3A THROUGH 3C EXCEPT AS NOTED)
CAP(S) ONLY
CAP(S) AND
ONE DEVICE
CAP(S) AND
TWO DEVICES
CAP (OPT) AND
THREE DEVICES
FOUR
DEVICES
BLANK OPENING (NO CABLES) :
1.2
1.3
2.6
3.2
4.5
OPENINGS WITH ANY
COMBINATION OF ITEM 5
CABLES FOR MAX 33%
AGGREGATE FILL IN DEVICE
TYPES 3B AND 3C, AND/OR MAX
100% VISUAL CABLE FILL IN
DEVICE TYPE 3A
-
2.6
5.1
7.7
NMKO
CAP(S) ONLY
CAP(S) AND ONE
CP 653 DEVICE
(ITEM 3A)
CAP(S) AND TWO
CP 653 DEVICES
(ITEM 3A)
CAP (OPT) AND
THREE CP 653
DEVICES (ITEM 3A)
FOUR CP 653
DEVICES
(ITEM 3A)
OPENINGS WITH MAX 100%
VISUAL CABLE FILL WITH
CABLE TYPE 5D ONLY AND
CP 653 ONLY
-
1.9
3.8
5.1
7.0