Page text
Sheet
Drawing No.
HILTI, Inc.
Date
Scale
3. ONE OF THE FOLLOWING TO BE INSTALLED WITHIN EACH CIRCULAR OPENING PORT OF THE HILTI
CFS-SL GP FIRESTOP GANGPLATE. THE TWO INTEGRAL SET SCREWS ARE TO BE TIGHTENED TO FIRMLY
BEAR AGAINST EACH DEVICE TO RETAIN IT IN POSITION.
A. HILTI CP 653 SPEED SLEEVE (4") CENTERED WITHIN WALL. INNER FABRIC SEAL SHOULD BE
TWISTED CLOSED.
B. HILTI CFS-SL RK FIRESTOP RETROFIT SLEEVE (4") CENTERED WITHIN WALL (ALSO SEE ITEM NO. 6).
C. HILTI CFS-SL SK FIRESTOP SLEEVE (4") CENTERED WITHIN WALL (ALSO SEE ITEM NO. 6).
4. [NOT SHOWN] HILTI CFS-SL CAP FIRESTOP GANGPLATE CAP TO BE INSTALLED TO CLOSE PORT
OPENINGS WHERE NO DEVICES ARE INSTALLED. PLATE INSTALLED PER ACCOMPANYING INSTALLATION
INSTRUCTIONS.
5. [OPTIONAL] CABLE BUNDLES TO BE A COMBINATION OF ANY OF THE FOLLOWING :
A. MAXIMUM 100 PAIR NO. 24 AWG TELEPHONE CABLE WITH PVC JACKET.
B. MAXIMUM 7/C NO. 12 AWG COPPER CONDUCTOR CONTROL CABLE WITH PVC OR XLPE JACKET AND
INSULATION.
C. MAXIMUM 4/0 AWG TYPE RHH GROUND CABLE.
D. MAXIMUM 4 PAIR NO. 22 AWG CAT 5 OR 6 COMPUTER CABLE.
E. MAXIMUM RG 6/U COAXIAL CABLE.
F. MAXIMUM 1/2" DIAMETER FIBER-OPTIC CABLE (24 FIBER) WITH PVC OR PE JACKET AND INSULATION.
G. MAXIMUM 3/C NO. 12 AWG MC CABLE.
6. HILTI CFS-PL FIRESTOP PLUG (2" OR 4") CUT TO FIT AROUND THE CABLE BUNDLE AND INSTALLED
TIGHTLY WITHIN HILTI FIRESTOP RETROFIT SLEEVE OR FIRESTOP SLEEVE FLUSH WITH THE END OF THE
SLEEVE ON BOTH SIDES OF THE WALL.
NOTE : CABLES MAY REPRESENT 0% TO 60% OF CROSS-SECTIONAL AREA
OF DEVICE FOR EACH CFS-RK AND CFS-SL SK FIRESTOP DEVICE
AND 0% TO 100% VISUAL FILL FOR EACH CP 653 SPEED SLEEVE.
WJ
POMM~
2 of 3
-
Jan. 28, 2013
UL/cUL SYSTEM NO. W-J-3200
F-RATING = 2-HR.
T-RATING = 1/4-HR.
L-RATING = SEE TABLE BELOW
tgPOMM~KMNOUNP
MULTIPLE CABLE BUNDLES THROUGH CONCRETE OR BLOCK WALL ASSEMBLY
Tulsa, Oklahoma USA (800) 879-8000
FIRESTOP DEVICE
MAXIMUM OPENING SIZE
24" PLATE :
SINGLE
5-1/2" x 20-1/2"
DOUBLE (STACKED)
13-1/4" x 20-1/2"
16" PLATE :
SINGLE
5-1/2" x 15"
DOUBLE (STACKED)
13-1/4" x 15"