Page text
Sheet
Drawing No.
HILTI, Inc.
Date
Scale
CAJ
1 of 2
11/64" = 1"
UL/cUL SYSTEM NO. C-AJ-3320
F-RATING = 2-HR.
T-RATING = 1/4-HR. OR 3/4-HR.
L-RATING = (SEE TABLE BELOW)
CABLE BUNDLE THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL ASSEMBLY
A
SECTION A-A
TOP VIEW
Tulsa, Oklahoma USA (800) 879-8000
A
1
2
3
4
A
SECTION A-A
BOTTOM VIEW
A
1
2
3
4
1. CONCRETE FLOOR OR WALL ASSEMBLY (2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR OR WALL (MINIMUM 2-1/2" THICK).
B. ANY UL/cUL CLASSIFIED PRECAST (HOLLOW-CORE) CONCRETE FLOOR (MINIMUM 6" THICK).
C. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
3320c
Sep. 18, 2013
CAJ3320c.091813