4. Cables — Cables to be rigidly supported on both sides of floor or wall assembly. Any combination of the following types and sizes of copper
conductor (unless otherwise noted) cables may be used, except that the total number of cables of types E, F and G below shall not exceed six (6).
Within each firestop device, cables shall be used for a total visual cable fill of 100 percent (one cable in each cable module within the device).
A. Max RG 6/U coaxial cable with fluorinated ethylene insulation and jacketing.
B. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation.
C. Max 24 fiber fiber optic cable with polyvinyl chloride (PVC) or polyethylene (PE) jacket and insulation having a max diam of 1/2 in. (13 mm).
D. Max 3/C with ground No. 8 AWG (or smaller) copper conductor NM cable (Romex) with PVC insulation and jacket.
E. Max 4/0 AWG 600V aluminum Type XHHW-2 ground cable with XLPE jacket and insulation.
F. Max 150 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation.
G. Max 7/C with ground, 600 V, No. 10 AWG (or smaller) copper conductor, aluminum armor TECK 90 cable with XLPE insulation and PVC
inner/outer jacket.
The T, FT and FTH Rating of the firestop system is 1 hr except that when cable types B, F and/or G are used, the T, FT and FTH Rating is ½ hr.
*Bearing the UL Classification Mark
CAJ 4025
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
November 12, 2012
System No. C-AJ-3319