CAJ 3283 (L) 1" Ann.Sp. Sealent Top or Bottom — page 407

Page text

Sheet
Drawing No.
HILTI, Inc.
Date
Scale
2. CABLE BUNDLE TO BE A COMBINATION OF ANY OF THE FOLLOWING :
A. MAXIMUM 100 PAIR NO. 24 AWG TELEPHONE CABLE WITH PVC JACKET.
B. MAXIMUM 7/C NO. 12 AWG COPPER CONDUCTOR CONTROL CABLE WITH PVC OR XLPE JACKET AND
INSULATION.
C. MAXIMUM 4/0 AWG SHIELDED PRINTER CABLE WITH PVC JACKET.
D. MAXIMUM 4 PAIR NO. 22 AWG CAT 6 COMPUTER CABLE.
E. MAXIMUM RG 6/U COAXIAL CABLE.
F. MAXIMUM 1/2" DIAMETER FIBER-OPTIC CABLE (24 FIBER) WITH PVC OR PE JACKET AND INSULATION.
G. MAXIMUM 20/C NO. 22 AWG SHIELDED PRINTER CABLE WITH PVC JACKET.
H. MAXIMUM 2/C NO. 18 AWG POWER OR NON-POWER LIMITED FIRE ALARM CABLE WITH OR WITHOUT
METAL JACKET (MANUFACTURED BY AFC CABLE SYSTEMS, INC).
I. MAXIMUM 1/4" DIAMETER S-VIDEO CABLE CONSISTING OF MAXIMUM 24 AWG 75 OHM COAX OR
TWISTED PAIR CABLE WITH PE INSULATION AND PVC JACKET.
3. HILTI CP 653 SPEED SLEEVE (2" OR 4") SLID INTO AND CENTERED WITHIN FLOOR OR WALL. DEVICE
FLANGES SPUN CLOCKWISE ONTO DEVICE THREADS OVER SMOKE GASKET, BUTTING TIGHTLY TO TOP
SIDE OF FLOOR, OR BOTH SIDES OF WALL. DEVICE FLANGE MAY BE INSTALLED ON BOTTOM SIDE OF
FLOOR WHEN HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT IS USED ON BOTTOM OF FLOOR.
4. SECURE DEVICE FLANGE TO TOP OF FLOOR WITH TWO 1-1/4" LONG CONCRETE SCREWS OR ANCHORS.
NOTES : 1. MAXIMUM DIAMETER OF OPENING = 3" (FOR 2" DEVICE) OR 5" (FOR 4" DEVICE).
2. CABLES MAY REPRESENT 0 TO 100% VISUAL FILL OF DEVICE.
3. MINIMUM ANNULAR SPACE BETWEEN DEVICE AND PERIPHERY OF OPENING = 0".
4. [OPTIONAL] AS AN ALTERNATE TO SMOKE GASKET MINIMUM 1/2" DEPTH HILTI
FS-ONE INTUMESCENT FIRESTOP SEALANT FLUSH WITH TOP SURFACE OF FLOOR
WITH AN ADDITIONAL 1/4" BEAD APPLIED AT POINT OF CONTACT. FIRESTOP
SEALANT IS REQUIRED ON BOTH SIDES OF A WALL.
5. [OPTIONAL] AS AN ALTERNATE TO FS-ONE, HILTI CP 618 FIRESTOP PUTTY MAY BE
INSTALLED ON TOP SIDE OF FLOOR, OR BOTH SIDES OF A WALL.
6. L-RATING APPLIES ONLY WHEN HILTI FS-ONE OR SMOKE GASKET IS USED.
CAJ
2 of 2
-
CABLE BUNDLE THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL ASSEMBLY
Tulsa, Oklahoma USA (800) 879-8000
UL/cUL SYSTEM NO. C-AJ-3283
F-RATING = 2-HR.
T-RATING = 1/2-HR.
L-RATING AT AMBIENT = LESS THAN 1 CFM (SEE TABLE)
L-RATING AT 400°F = LESS THAN 1 CFM (SEE TABLE)
SEALANT / GASKET
SEALANT / GASKET
MAX CABLE
FILL
CABLE TYPE
L RATING, CFM/SQ FT
L RATING, CFM
AMBIENT
400°F
AMBIENT
400°F
0%
—
1
2
LESS THAN 1LESS THAN 1
100%
ANY CABLES (ITEM NO. 2)
IN ANY COMBINATION
7
7
LESS THAN 1LESS THAN 1
3283d
Aug. 13, 2014
CAJ3283d.081314