Page text
Sheet
Drawing No.
HILTI, Inc.
Date
Scale
CAJ
3283d
1 of 2
13/64" = 1"
Aug. 13, 2014
UL/cUL SYSTEM NO. C-AJ-3283
F-RATING = 2-HR.
T-RATING = 1/2-HR.
L-RATING AT AMBIENT = LESS THAN 1 CFM (SEE TABLE)
L-RATING AT 400°F = LESS THAN 1 CFM (SEE TABLE)
CAJ3283d.081314
CABLE BUNDLE THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL ASSEMBLY
A
A
SECTION A-A
TOP VIEW
Tulsa, Oklahoma USA (800) 879-8000
1
3
2
4
1. CONCRETE FLOOR OR WALL ASSEMBLY (2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR OR WALL (MINIMUM 2-1/2" THICK).
B. STEEL FLOOR UNIT/FLOOR ASSEMBLY - LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR
(MINIMUM 2-1/2" THICK).
C. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.