Page text
Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
NOTES : 1. CLOSED OR VENTED PIPING SYSTEM (PVC, ABS, FRPP = SCH 40; CPVC = SDR 11, 13.5, OR 17).
2. FOR CONCRETE FLOOR OVER METAL DECKING APPLICATIONS, A METAL DECK ADAPTER KIT
IS REQUIRED.
3. ABS AND FRPP PLASTIC PIPE MAY ONLY BE INSTALLED IN MINIMUM 4-1/2" THICK CONCRETE
FLOORS. FT AND FTH RATINGS ARE 0-HR. WHEN ABS AND FRPP PIPES ARE USED.
4. L-RATING APPLIES ONLY WHEN DIAMETER OF PIPE EQUALS SIZE OF DEVICE (3" PIPE IN 3"
DEVICE, ETC.).
5. [OPTIONAL] TO OBTAIN 2-HR. FT RATING ON ABS OR PVC PLASTIC PIPES (3" AND SMALLER)
WHERE FT RATING IS LISTED AS LESS THAN 2-HRS. IN TABLE ABOVE A 1/2" THICK PIECE OF
GLASS-FIBER PIPE INSULATION MAY BE SECURED TO PIPE AT THE TOP OF THE FLOOR
EXTENDING MINIMUM 12" ABOVE THE FLOOR SURFACE. PIPE INSULATION SECURED WITH
METAL FASTENERS OR BUTT TAPE. WHEN (NOMINAL) PIPE DIAMETER IS LESS THAN DEVICE
SIZE MINIMUM 1-1/4" THICKNESS MINERAL WOOL (MIN. 4 PCF DENSITY) SHALL BE TIGHTLY
PACKED INTO HILTI CP 680-P FLUSH WITH TOP SURFACE OF DEVICE.
cUL
2 of 2
-
cUL SYSTEM NO. F-A-2012
CANADA ONLY
MINIMUM CONCRETE
THICKNESS
NOMINAL PIPE DIAMETER
PRODUCT DESCRIPTION
RATINGS, HR.
F
FH
FT
FTH
OJNLO?
2" (PVC OR CPVC ONLY)
CP 680-P 2"
2
0
3/4
0
OJNLO?
3" (PVC OR CPVC ONLY)
CP 680-P 3"
2
0
0
0
OJNLO?
4" (PVC OR CPVC ONLY)
CP 680-P 4"
2
0
0
0
OJNLO?
6" (PVC OR CPVC ONLY)
CP 680-P 6"
2
0
0
0
4-1/2"
1-1/2"
CP 680-P 2"
2
0
2
0
4-1/2"
2"
CP 680-P 2"
2
0
2
0
4-1/2"
3"
CP 680-P 3"
3
0
0
0
6"
3" (PVC OR CPVC ONLY)
CP 680-P 3"
2
2
2
2
4-1/2"
3"
CP 680-P 4"
3
3
2
2
4-1/2"
4"
CP 680-P 4"
3
3
2
2
4-1/2"
4"
CP 680-P 6"
1
0
0
0
4-1/2"
6"
CP 680-P 6"
2
0
0
0
PLASTIC PIPE THROUGH CONCRETE FLOOR/CONCRETE OVER METAL DECKING
F-RATING = 1-HR., 2-HR., OR 3-HR.
FH-RATING = 0-HR. OR 3-HR.
FT-RATING = 0-HR., 1/4-HR., 3/4-HR., OR 2-HR.
FTH-RATING = 0-HR. OR 2-HR.
L-RATING AT AMBIENT = LESS THAN 1 CFM/SQ FT
L-RATING AT 400° F = LESS THAN 1 CFM/SQ FT
NOTE : TESTED WITH A 50 Pa PRESSURE DIFFERENTIAL
Feb. 14, 2014
cUL FA2012k.021414