Page text
Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
cUL
1 of 2
5/32" = 1"
Feb. 14, 2014
cUL SYSTEM NO. F-A-2012
cUL FA2012k.021414
PLASTIC PIPE THROUGH CONCRETE FLOOR/CONCRETE OVER METAL DECKING
CANADA ONLY
F-RATING = 1-HR., 2-HR., OR 3-HR.
FH-RATING = 0-HR. OR 3-HR.
FT-RATING = 0-HR., 1/4-HR., 3/4-HR., OR 2-HR.
FTH-RATING = 0-HR. OR 2-HR.
L-RATING AT AMBIENT = LESS THAN 1 CFM/SQ FT
L-RATING AT 400° F = LESS THAN 1 CFM/SQ FT
NOTE : TESTED WITH A 50 Pa PRESSURE DIFFERENTIAL
A
SECTION A-A
TOP VIEW
1. CONCRETE FLOOR ASSEMBLY (1-HR., 2-HR. OR 3-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR (MIN. 2-1/2", 4-1/2", OR 6" THICK).
B. STEEL FLOOR UNIT/FLOOR ASSEMBLY - LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE
FLOOR (MIN. 2-1/2", 4-1/2", OR 6" THICK) OVER METAL DECKING.
2. PENETRATING ITEM TO BE ONE OF THE FOLLOWING (SEE TABLE BELOW):
A. MAXIMUM 6" NOMINAL DIAMETER PVC PLASTIC PIPE (CELLULAR AND SOLID CORE).
B. MAXIMUM 4" NOMINAL DIAMETER ABS PLASTIC PIPE (CELLULAR AND SOLID CORE)
(SEE NOTE NO. 3 BELOW).
C. MAXIMUM 6" NOMINAL DIAMETER FRPP PLASTIC PIPE (SEE NOTE NO. 3 BELOW).
D. MAXIMUM 6" NOMINAL DIAMETER CPVC PLASTIC PIPE (SDR 11, SDR 13.5, OR SDR 17).
E. MAXIMUM 6" NOMINAL DIAMETER AQUARISE CPVC PLASTIC PIPE (SDR 11) MANUFACTURED
BY IPEX, INC. (CLOSED PIPING SYSTEM ONLY).
F. MAXIMUM 4" NOMINAL DIAMETER RIGID NONMETALLIC CONDUIT (SCH 40 PVC).
G. MAXIMUM 6" NOMINAL DIAMETER SYSTEM 15 PVC PLASTIC PIPE (CELLULAR OR SOLID CORE)
MANUFACTURED BY IPEX, INC.
3. HILTI CP 680-P CAST-IN FIRESTOP DEVICE, CAST OR GROUTED INTO CONCRETE FLOOR
(SEE TABLE BELOW).
A
1
2
3
MAX. 2"