INTRODUCTION
APPLICATIONS / PRODUCTS
SYSTEM DETAILS
ESTIMATING TABLES / TECH DATA
Saving Lives through innovation & educationR Hilti Firestop Guide 2005–2006R 1-800-363-4458R www.ca.hilti.com
24
1. Clean penetration
2. Wrap strips around
pipe the specified
number of times
3. Push Wrap Strips
into hole
4. Seal penetration
against smoke with
FS-ONE
5. Fasten installation
plate (If required)
Firestop
System
sodfm,eviJdjfiwhriuh.NöoWE
Z8Z23awöp3i4eß0288u27uze
4i5kirdwiloi4jtf-öx-.vbvbvh,ireiv
u9+ß12oeoo
CP648Brandschutzmansch.
Product description
•
An intumescent, flexible firestop wrap strip for plastic and
insulated pipe penetrations
Product features
•
Highly Intumescent
•
Long length avoids waste
•
Can be continuously wrapped
•
Cost effective
Areas of application
•
Firestopping combustible pipe penetrations
•
Difficult applications where space is limited
•
Penetrations through concrete over metal deck
•
Plastic and insulated penetrations using
PVC, CPVC, ABS, FRPP and PEX
For use with
•
Concrete, masonry, wood floor and gypsum wall assemblies
•
Wall and floor assemblies rated up to 4 hours
Examples
•
Waste water pipes
•
Fresh water pipes
•
Decking penetrations
CP 648-E
Technical Data
At 73°F (23°C) and 50% relative humidity
Density
Approx. 1.35 g/cm3
Dimensions (Approximate)
3/16" x 1" x 33 ft or
3/16" x 1-3/4" x 33 ft
Color
Black with foil backing
Temperature resistance
–40°F to 212°F (–20°C to 100°C)
Intumescent activation
Approx. 320°F (160°C)
Expansion ratio (unrestricted)
1:40
Surface burning characteristics
(ASTM E 84-96)
Flame Spread Index: In progress
Smoke Development Index: In progress
Tested in accordance with
• UL 1479
• ASTM E 814
• ASTM E 84
• ULC-S115-95
* CAN4-S115-95M
Internationally tested and approved
CP 648-E
Firestop Wrap Strip
Opening
1.Clean the plastic pipes or insulated pipe penetration.
Expansion of the intumescent material during a fire acts
to close the plastic pipe or pipe penetration. Very dirty
pipes with, for example, remains of mortar, may lead to
a delay in this closing action.Soiled plastic pipes or
insulated pipe penetrations should, therefore, be cleaned
in the area where the CP 648-E Firestop Wrap Strip is to
be installed.
Application of firestop system
2.Tightly wrap the required number of strips continuously
around the penetrant, and hold in place with tape.
3.Push the Hilti Wrap Strip into the opening until it is flush
with the substrate surface unless otherwise required by
the UL or cUL system. It may be required by the UL or
cUL system to clamp, wire or use a Hilti Retaining Collar
to secure the wrap strip in place for some applications.
4.If the UL or cUL system requires a cold smoke seal, then
apply the proper amount of Hilti FS-ONE sealant in the
opening over the wrap strip.
5.For maintenance reasons,a penetration seal can be
permanently marked with an identification plate and
fastened in a visible position next to the seal.
Notice about approvals
•When making a pipe seal using Hilti CP 648-E Firestop
Wrap Strip,please refer to the UL/cUL Fire Resistance
Directory or the Hilti Firestop Manual for complete
details, including restrictions as to opening size, type and
thickness of wall or floor, maximum pipe diameter, etc.
Not for use...
•In highly corrosive surroundings
•With unapproved retaining collars, anchors/fasteners
Safety precautions
•Read the Material Safety Data Sheet
•Keep out of the reach of children
Storage
•Store only in the original packaging in a location
protected from moisture at temperatures between
23°F and 86°F (–5°C and 30°C).
Installation instructions for CP 648-E
System Advantage / Customer Benefits
•
Quick and easy closure without tools
•
Ideal for very tight installations
FILL, VOID OR CAVITY MATERIAL
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
FM
APPROVED
| latest product information :
www.ca.hilti.com
| ordering information see page:
31