Product description
•
Ready to use Firestop Board designed for large openings with
cable trays and multiple penetrations
Product features
•
Lightweight design
•
Variety of tested systems
•
Systems for one-sided installation
Areas of application
•
Temporary or permanent sealing of cables and cable tray
penetrations
•
Sealing single or multiple penetrations in large openings
•
Temporary or permanent sealing of large blank openings
For use with
•
Concrete, concrete block, and gypsum wall assemblies
•
Concrete floor assemblies
Examples
•
Locations where telecommunications and electrical
applications are modified on a regular basis such as central
office facilities, computer data centers, commercial buildings,
healthcare facilities, and laboratories.
•
New buildings under construction and during renovation
NEW!
CP 675T
Technical Data
Color
Red
Size
26" x 39" x 1" (Large Board)
(660 mm x 990 mm x 25 mm)
26" x 28" x 1" (Small Board)
(660 mm x 711 mm x 25 mm)
Density
320 kg/m3
Application Temperature
-22°F to 176°F (-30°C to 80°C)
Temperature Resistance
-22°F to 176°F (-30°C to 80°C)
Surface burning characteristics
(ASTM E 84-00)
Flame Spread Index: 5
Smoke Development Index: 10
Tested in accordance with
• UL 1479
• ASTM E 814
• ASTM E 84
• CAN4-S115-95M
• ULC-S115-95M
Internationally tested and approved
System Advantage / Customer Benefits
•Satisfies a wide range of application
scenarios
•Allows for high flexibility and eases re-
penetration / cable mining from one
side of the wall
•Easy and fast cable re-penetration and
cable mining with reduced labor and
materials
•Labor saving “one person, one sided
installation” method
•Polyurethane foam material, easy to
cut without electric tools
•No dust, no fibers, no mess
•Same system for all types of wall
materials
Surface Mounted Installation (wall)
1.Clean the opening.
2.Measure the size of the opening.
Cut the Firestop
Board to size (check system for overlap requirements)
with a utility knife, hand saw, circular saw, jig saw, or
table saw.
3.If penetrants run through the opening, cut the Firestop
Board correspondingly (max.annular space between
Board and penetrant: 1/2”).The Board can be cut into
two pieces or just cut to allow space for the
penetrant(s).
4.Apply CP 619T Putty Roll around edges of the Firestop
Board next to the wall.In case of penetrants, the cables
and cable trays have to be sealed with CP 619T Putty
Roll at their interface with the Firestop Board.
5.Attach Firestop Board with approved Hilti anchors as
specified in accordance with the applicable firestop
system.When two Firestop Boards come together, seal
intersection with CP 619T Putty Roll or FS-ONE (per
firestop system requirements).
6.Fasten identification plate (if required).
7.Repeat steps on other side of wall.
Frame Mounted Installation (wall)
1.Clean the opening.
2.Measure the size of the opening.Cut the CP 675T Z-
Frame component to size and attach to top and both
sides of opening as specified by firestop system with
appropriate Hilti fasteners.Apply CP 619T Putty Roll to
back lip of Z-Frame inside opening.
3.Apply a maximum of three rows (6”) of FS657 Fire
Blocks in the opening above and below cable tray
(lengthwise).Cut the CP 675T T-Separator Bar to the
width of the opening and put it on top of the FS 657 Fire
Blocks (T-edge against back of opening).
Apply
CP 619T Putty Roll to the backward T-Bar edge
protruding above the FS 657 Fire Block section and
around back lip of frames.
4.Cut Firestop Boards to size +1/2”vertically.Use the
extra 1/2” to compress the FS 657 Fire Block partition
and provide a tight fit into the opening.Place CP 675T
Distance Holders around Firestop Board at a maximum
of every 8”.With downward pressure,press top of
inside Firestop Board into opening and push flush with
back edge of Z-Frame followed by outside Firestop
Board inserted flush with wall surface.
5.Secure front of Firestop Board with Z-Frame Latches
every 8”.
Apply CP 619T Putty Roll over the
intersection between the Board and the Frame.
Fill
voids around penetrating items within FS 657 Fire
Block partition with Hilti Firestop Putty.Refer to UL/cUL
systems for complete details.
6.Fasten identification plate (if required).
Notice about approvals
•When installing Hilti CP 675T Firestop Board,please
refer to the UL Fire Resistance Directory or the Hilti
Firestop Manual for complete details such as
restrictions for opening size, type and thickness of wall
or floor, maximum size of cable tray, etc.
Not for use…
•In wet rooms,outdoors or in areas exposed to the
weather or UV radiation.
Safety precautions
•Keep out of the reach of children
•Read the Material Safety Data Sheet
Storage
•Store only in the original packaging in a location
protected from moisture and direct sunlight
Installation Instructions for CP 675T Firestop Board