Hilti CP 653
Speed Sleeve
Hilti, Inc. (U.S.)1-800-879-8000 • www.us.hilti.com• en español1-800-879-5000 www.us.hilti.com/espanol • Hilti (Canada) Corp.1-800-363-4458 www.hilti.ca
Hilti. Outperform. Outlast.
When easy
or quick
aren’t good
enough.
Healthcare managers, telecom and
datacom professionals, and electrical
trades understand the importance of life
safety and asset preservation. When
selecting the correct cable management
device, they know the right product
addresses a multitude of performance criteria. These aspects include fast product installation,
ease of cable penetration and re-penetration, superior ability to limit smoke migration whether
empty or 100% visual-fill, a wide portfolio of firestop details, and a robust, lightweight solution
that endures long-term, high-traffic usage. The Hilti CP 653 Speed Sleeve is a ready-to-use,
one-step cable management firestop device that addresses all of these needs.
Innovations
Fast installation
• Round openings can
be created via hole
saws or core bits
• “Spin on” flanges
promote fast product
installation
Fast cable installation
• Cables do not need to
be inserted in a
uniform height to
comply with the
firestop detail
Easy penetration and re-penetration
• Opening and closing the device is easy and
intuitive: from one side of the CP 653, depress
the red tabs and twist the inner housing
Extremely low L-ratings
• Constrictive smoke
seal limits smoke
migration:
- Less than 1 cfm/ft2
for empty device
- 5 cfm/ft2possible for
cable bundles
Withstands the rigors
of usage and time
• Robust smoke seal
fabric tested to 250
open-close cycles
Ordering Information
Item No.
Description
Qty
OPSPOP
CP 653 2" Speed Sleeve
1
OPSPOQ
CP 653 4" Speed Sleeve
1
Always refer to the MSDS before use and the UL Fire
Resistance Directory or Hilti Firestop Systems Guide for
complete installation information.
1.Use either a 2.5" or 4.5" hole saw to create the
appropriate hole.
2. Insert the sleeve.
3. Seal the gap with firestop sealant to impede smoke
and gas migration. Repeat on other side of the wall
4. Spin the flange clockwise onto the device. Repeat on
other side of the wall.
5. To open the device:
(a) On one side of the wall, press the clip closures
inward.
(b) Twist the device counterclockwise.
6. To close the device:
(a) On the same side of the wall, press the clip
closures inward.
(b) Twist the device clockwise until finger-tight,
allowing it to engage with a click.
For repenetration of cables, repeat steps 5 & 6.
For installation options not presented here, consult your
local Hilti representative for other rated firestop systems.
Installation Instructions
1
2
3
4
5
6
CP 653 Technical Data
Device
OD (device only)
OD (flange)
ID
Total length
Weight (device and flanges)
2"
2.3 in
4.7 in
1.7 in
12.4 in
1.5 lbs
4"
4.3 in
6.7 in
3.7 in
12.4 in
2.6 lbs
Density
Approx. 1.35 g/cm3
Temperature resistance
22°F to 212°F (-30°C to 100°C)
Intumescent activation
Approx. 320°F (160°C)
Expansion ratio (unrestricted)
1:40
Metal
Steel with zinc coating
Plastic
ABS
Fabric
Glass-fiber
Approvals
California State Fire Marshal
In Progress
City of New York
In Progress
Internationally tested and approved
FM
APPROVED