Division 07 – Thermal and Moisture Protection
OPL Design No. CEJ 425 P
07 84 00 Fire stopping
07 84 53 Building Perimeter Fire stopping
Page 5 of 6
Date Revised: November 5, 2010
©Intertek
Project No: G100141291SAT-007
the steel-stud framing (Item 2B) in
accordance with the manufacturer’s
installation
instructions.
When
framing for the aluminum panels is
required, it is to be installed with the
manufacturer’s
installation
instructions.
The
system
is
a
monolithic
assembly
without
expansion or control joints.
(4) Brick: Use any conventional
brick and mortar type. Any brick
pattern is acceptable. Mortar joints
not to exceed 7/8 in.. Secure bricks
to wall assembly using conventional
acceptable masonry construction
techniques.
The
system
is
a
monolithic
assembly
without
expansion or control joints.
(5) Stucco: Any Listed and Labeled
stucco
system
is
acceptable
provided that the following is abided
by: When EPS is used, the EPS
foam boards nominally measure a
max. of 4 in. thick with a nominal
density
of
1
pcf.
The
stucco
manufacturer confirms the stucco is
compatible with the sandwiched wall
surface. The system is a monolithic
assembly
without
expansion
or
control joints.
(6) Stone: Use any conventional
stone
panel
and
mortar
type
measuring at least 1 in. thick. Any
stone pattern is acceptable. Mortar
joints not to exceed 7/8 in.. Secure
stones to wall assembly using
conventional acceptable masonry
construction
techniques.
The
system is a monolithic assembly
without expansion or control joints.
(7) Siding: Any Listed and Labeled
siding
system
is
acceptable
provided that the following is abided
by: The siding shall be classified as
non-combustible. The system is a
monolithic
assembly
without
expansion or control joints.
(8) GFRC Panels: Glass fiber
reinforced concrete panels shall be
at least 1 in. thick and attached in
accordance with the manufacturer’s
installation instructions. The system
is a monolithic assembly without
expansion or control joints.
(9) Roofing Materials: Any Listed
and Labeled Class A bituminous
roofing
material
applied
in
accordance
with
manufacturer’s
installation
instructions.
Only
Intertek
Certified
Roofing
Manufacturer’s product meeting the
above min. requirements.
3. PERIMETER
JOINT
PROTECTION:
The perimeter joint (linear opening) shall
not exceed a 2 in. nom. joint width (joint
width at installation) between the interior
face of the sandwiched wall surface and
the vertical face of the concrete floor
assembly. The perimeter joint treatment
shall
incorporate
the
following
construction features:
A. Packing Material: Use a min. 4 in.
thick, 4 pcf density, mineral wool
batt
insulation.
Install
the
top
surface of the packing material flush
with the top and bottom surface of
the concrete floor assembly (Item
1). Only Intertek Certified Mineral
Wool
Manufacturer’s
product
meeting
the
above
min.
requirements. Compress the lengths
of packing material together at least
1/2 in. at splices (butt joints). Install
packing material (Item 3A) using the
following method: Install the packing
material in the reveal created by the
cantilevered tracks (Items 2B above
the floor & 2C below the floor) and
reinforcing angle (Item 3C). Install
pieces of packing material (Item 3A)
with fibers running vertically with the
slip-track (deflection channel) (Item
2C). Cut lengths of the packing
material a min. of 4-1/4 in. high by
min. 2-1/4 in. wide for min. 4 in. by 2
in.
reveal.
Use
proportionate
packing material for larger reveals.
Overlap and compress the ends of