Page text
Division 07 – Thermal and Moisture Protection
OPL Design No. CEJ 425 P
07 84 00 Fire stopping
07 84 53 Building Perimeter Fire stopping
Page 1 of 6
Date Revised: November 5, 2010
©Intertek
Project No: G100141291SAT-007
Design Number HI/BP 120-04
PERIMETER FIRE BARRIER SYSTEM
Hilti, Inc.
ASTM E 2307
Table 1
Firestop
Joint Spray
CFS-SP WB
Silicone
Joint Spray
CFS-SP SIL
F-Rating
2 hr
2 hr
T-Rating
1 hr
1 hr
Application
Thickness
1/8" wet film
(1/16" dry)
2mm (0.079")
wet film
Cycling (%)
Horizontal
Vertical
See Note 1
± 11.25
± 5
± 7.5
± 5
HEAD OF WALL JOINT SYSTEM
ASTM E 2307-04 Section 14.1 Movement
L-Rating <1.0 SCFM/LF
Rated for ± 0 % horizontal movement
Rated for - 100% downward vertical shear movement (3/4 in.) Class II 500 Cycles
Rated for + 0% upward vertical shear movement