Division 07 – Thermal and Moisture Protection
OPL Design No. CEJ 421 P
07 84 00 Fire stopping
07 84 53 Building Perimeter Fire stopping
Page 1 of 6
Date Revised: June 20, 2013
©Intertek
Project No: G100141291SAT-007
Design Number HI/BP 120-03
PERIMETER FIRE BARRIER SYSTEM
Hilti, Inc.
ASTM E 2307
Table 1
Firestop
Joint Spray
CFS-SP WB
Silicone
Joint Spray
CFS-SP SIL
F-Rating
2 hr
2 hr
T-Rating
1 hr
1 hr
Application
Thickness
1/8" wet film
(1/16" dry)
2mm (0.079")
wet film
Cycling (%)
Horizontal
Vertical
See Note 1
None
None
None
None
L-Rating <1.0 SCFM/LF
1. CONCRETE FLOOR ASSEMBLY: Min.
two-hour rated concrete floor assembly
(Item 1) made from either lightweight or
normal weight concrete with a density of
100-150 pcf, with a min. thickness of 4-
1/2 in. at the slab edge (joint face).