CEJ 314P - (L) Speed Spray (1/8") 2 3/4 Hr - 6" max — page 1209

Page text

Division 07 – Thermal and Moisture Protection
OPL Design No. CEJ 314 P
07 84 00 Fire stopping
07 84 53 Building Perimeter Fire stopping
Page 1 of 3
Date Revised: June 20, 2014
©Intertek
Project No: 100141291SAT-007
Design Number HI/BP 165-01
PERIMETER FIRE BARRIER SYSTEM
Hilti, Inc.
ASTM E 2307
Table 1
Firestop
Joint Spray
CFS-SP WB
Silicone
Joint Spray
CFS-SP SIL
F-Rating
2-3/4 hr
2-3/4 hr
T-Rating
1 hr
1 hr
Application
Thickness
1/8" wet film
(1/16" dry)
2mm (0.079")
wet film
Cycling (%)
Horizontal
Vertical
See Note 1
± 8.3
± 5
± 7.5
± 5
L-Rating <1.0 SCFM/LF
1.  CONCRETE FLOOR ASSEMBLY: Max.
two-hour rated concrete floor assembly
made from either lightweight or normal
weight concrete with a density of 100-
150 pcf, with a min. thickness of 4-1/2
in.  at the joint face.  Overall slab
thickness may vary to accommodate
various blockout depths (longitudinal
recesses) formed in the concrete, to
house the architectural cover plate. The