Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
A
A
NOTE : MAXIMUM WIDTH OF JOINT = 2".
1. CONCRETE WALL ASSEMBLY (4-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL (MINIMUM 6" THICK).
B. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
2. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR (MINIMUM 6" THICK) (4-HR. FIRE-RATING).
3. MINIMUM 5" THICKNESS MINERAL WOOL SAFING (MIN. 4 PCF DENSITY) COMPRESSED MINIMUM 50%.
4. MINIMUM 1/2" DEPTH HILTI CFS-S SIL GG FIRESTOP SILICONE SEALANT, HILTI CP 601S ELASTOMERIC
FIRESTOP SEALANT, OR HILTI CFS-S SIL SL FIRESTOP SILICONE SEALANT.
FWD
1047c
1 of 1
5/32" = 1"
Feb. 14, 2014
UL/cUL SYSTEM NO. FW-D-1047
F-RATING = 4-HR.
CLASS II MOVEMENT CAPABILITES - 12.5% COMPRESSION OR EXTENSION
FWD1047c.021414
FIRE-RATED JOINT THROUGH CONCRETE FLOOR ASSEMBLY
1
2
3
4
SECTION A-A
TOP VIEW