NOTE : MAXIMUM WIDTH OF JOINT = 3-1/2".
1. CONCRETE WALL ASSEMBLY (3-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL (MINIMUM 4-1/2" THICK).
B. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
2. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR (MINIMUM 4-1/2" THICK) (3-HR. FIRE-RATING).
3. MINIMUM 4-1/4" THICKNESS MINERAL WOOL SAFING (MIN. 4 PCF DENSITY) COMPRESSED MINIMUM 42%.
4. MINIMUM 1/4" DEPTH HILTI CFS-S SIL GG FIRESTOP SILICONE SEALANT, HILTI CP 601S ELASTOMERIC
FIRESTOP SEALANT, OR HILTI CFS-S SIL SL FIRESTOP SILICONE SEALANT.
FWD
1011g
1 of 1
5/32" = 1"
Feb. 14, 2014
UL/cUL SYSTEM NO. FW-D-1011
F-RATING = 3-HR.
CLASS II MOVEMENT CAPABILITES - 14% COMPRESSION OR EXTENSION
FWD1011g.021414
FIRE-RATED JOINT THROUGH CONCRETE FLOOR ASSEMBLY