Page text
Sheet
Drawing No.
R
FIRESTOP SYSTEMS
HILTI, Inc.
Tulsa, Oklahoma USA (918) 252-6000
Date
Scale
Saving Lives through Innovation and Education
CROSS-SECTIONAL VIEW
NOTE : MAXIMUM WIDTH OF JOINT = 6".
1. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR ASSEMBLY (MINIMUM 4-1/2" THICK)
(2-HR. FIRE-RATING).
2. MINIMUM 4" THICKNESS MINERAL WOOL (MIN. 4 PCF DENSITY) COMPRESSED 50%.
3. MINIMUM 1/2" DEPTH HILTI CP 604 SELF LEVELING FIRESTOP SEALANT.
FFD
1039b
1 of 1
5/16" = 1"
June 15, 2005
UL/cUL SYSTEM NO. FF-D-1039
ASSEMBLY RATING = 2-HR.
CLASS II MOVEMENT CAPABILITIES = 10% COMPRESSION OR EXTENSION
FFD1039b.061505
FIRE-RATED JOINT THROUGH CONCRETE FLOOR ASSEMBLY
1
2
3