FFD 0052 - CP 606(1") No MW 2 Hr - 1/2" max — page 1114

Page text

Sheet
Drawing No.
R
FIRESTOP SYSTEMS
HILTI, Inc.
Tulsa, Oklahoma USA (918) 252-6000
Date
Scale
TOP VIEW
A
A
Saving Lives through Innovation and Education
SECTION A-A
NOTE : MAXIMUM WIDTH OF JOINT = 1/2".
1. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR ASSEMBLY (MINIMUM 4-1/2" THICK)
(2-HR. FIRE-RATING).
2. MINIMUM 1" DEPTH HILTI CP 606 FLEXIBLE FIRESTOP SEALANT.
FFD
MMRO~
1 of 1
1/8" = 1"
FEB. 04, 2005
FIRE-RATED JOINT THROUGH CONCRETE FLOOR ASSEMBLY
UL/cUL SYSTEM NO. FF-D-0052
ASSEMBLY RATING = 2-HR.
CLASS II MOVEMENT CAPABILITIES - 12.5% COMPRESSION OR EXTENSION