Page text
Sheet
Drawing No.
HILTI, Inc.
Date
Scale
HWD
1 of 2
9/64" = 1"
Mar. 17, 2011
ASSEMBLY RATING = 1-HR. OR 2-HR.
L-RATING AT AMBIENT = LESS THAN 1 CFM/LIN. FT.
L-RATING AT 400°F = LESS THAN 1 CFM/LIN. FT.
CLASS II OR III MOVEMENT CAPABILITIES - 50% COMPRESSION OR EXTENSION
TOP OF WALL JOINT : GYPSUM SHAFT WALL ASSEMBLY
CROSS-SECTIONAL VIEW
Tulsa, Oklahoma USA (800) 879-8000
MIN. 2 1/2"
MAX. 3"
MAX. 1 1/2"
MAX. 12"
1
2
3
4
5
1. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR ASSEMBLY (MINIMUM 2-1/2" THICK) OVER METAL
DECKING (UL/cUL CLASSIFIED D700 SERIES) (1-HR. OR 2-HR. FIRE-RATING).
2. STRUCTURAL STEEL BEAM, AS SPECIFIED IN THE INDIVIDUAL D700 SERIES DESIGN. STRUCTURAL
STEEL BEAM ORIENTED PARALLEL TO AND MAXIMUM 12" FROM WALL ASSEMBLY.
0636a
UL/cUL SYSTEM NO. HW-D-0636
HWD0636a.031711
6
7
8
7
8