Page text
Sheet
Drawing No.
HILTI, Inc.
Date
Scale
HWD
0218j
1 of 2
3/32" = 1"
Oct. 23, 2013
UL/cUL SYSTEM NO. HW-D-0218
ASSEMBLY RATING = 1-HR. OR 2-HR.
CLASS II MOVEMENT CAPABILITIES - 25% COMPRESSION OR EXTENSION
L-RATING AT AMBIENT = LESS THAN 1 CFM / LIN FT
L-RATING AT 400°F = LESS THAN 1 CFM / LIN FT
HWD0218j.102313
TOP OF WALL JOINT : GYPSUM WALL ASSEMBLY
B
B
SECTION A-A
FRONT VIEW
Tulsa, Oklahoma USA (800) 879-8000
1. FLOOR OR ROOF ASSEMBLY (1-HR. OR 2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR (MIN. 2-1/2" THICK) OVER METAL DECKING
(UL/cUL CLASSIFIED D700 OR D900 SERIES).
B. INSULATING CONCRETE (MIN. 2-1/4" THICK) OVER METAL DECKING (UL/cUL CLASSIFIED P900 SERIES).
C. [NOT SHOWN] FLUTED STEEL ROOF DECK WITH SPRAY-APPLIED FIREPROOFING (UL/cUL CLASSIFIED
P700 SERIES).
MAX. 3"
MIN. 2 1/2"
MAX. 1 1/2"
SECTION B-B
A
A
1
2
3
4
5
6
7
8
9
9