1. FLOOR OR ROOF ASSEMBLY (1-HR. OR 2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR (MIN. 2-1/2" THICK) OVER METAL DECKING.
B. INSULATING CONCRETE (MIN. 2-1/4" THICK) OVER METAL DECKING (UL/cUL CLASSIFIED P900 SERIES).
C. [NOT SHOWN] FLUTED STEEL ROOF DECK WITH SPRAY-APPLIED FIREPROOFING (UL/cUL CLASSIFIED
P700 SERIES).
2. GYPSUM WALL ASSEMBLY (UL/cUL CLASSIFIED U400 OR V400 SERIES) (1-HR. OR 2-HR. FIRE-RATING).
3. METAL DEFLECTION TRACK (MIN. 22 GA., 3" FLANGES) FASTENED TO UNDERSIDE OF THE DECK WITH
STEEL MASONRY ANCHORS, STEEL FASTENERS, OR WELDS (SPACED MAX. 24" O.C.). CEILING RUNNER
(1" FLANGES) INSTALLED WITHIN THE U-SHAPED DEFLECTION CHANNEL WITH A 1-1/2" GAP MAINTAINED
BETWEEN THE TOP OF THE CEILING RUNNER AND TOP OF DEFLECTION PLATE (SEE NOTE NO. 3 BELOW).
4. [OPTIONAL - NOT SHOWN] WHEN SPRAY-APPLIED FIREPROOFING IS USED, CEILING RUNNER MAY BE
SECURED TO DECK WITH Z-SHAPED CLIPS (MIN. 20 GA.) WITH THE FOLLOWING DIMENSIONS : MINIMUM 1"
LONG, BUT NOT EXCEEDING THE WIDTH OF THE WALL, BY 1-1/2" OR 2" LONG UPPER AND LOWER LEGS.
SUPPORT CLIPS SPACED MAXIMUM 24" OC.
5. STEEL STUDS (MINIMUM 2-1/2" WIDE), CUT 1/2" TO 3/4" LESS IN LENGTH THAN ASSEMBLY HEIGHT,
NESTING IN CEILING RUNNER WITHOUT ATTACHMENT.
6. HILTI CP 767 SPEED STRIPS OR MINERAL WOOL SAFING (MIN. 4 PCF DENSITY) COMPRESSED 50% AND
INSERTED INTO FLUTES, FLUSH WITH BOTH SIDES OF WALL.
7. MINIMUM 1/8" (WET) THICKNESS HILTI CFS-SP WB FIRESTOP JOINT SPRAY OR HILTI CP 672 SPEED SPRAY
TO COMPLETELY COVER MINERAL WOOL AND TO OVERLAP A MINIMUM OF 1/2" ONTO GYPSUM AND
METAL DECKING ON BOTH SIDES OF GYPSUM WALL ASSEMBLY.
NOTES : 1. MAXIMUM WIDTH OF JOINT = 2".
2. STEEL FLOOR UNITS MAY BE SPRAYED WITH A MINIMUM 5/16" TO MAXIMUM 1-3/4" THICKNESS
OF UL CLASSIFIED MONOKOTE TYPE MK-6/HY (MANUFACTURED BY W.R. GRACE) OR CAFCO
TYPE 300 (MANUFACTURED BY ISOLATEK, INT.) FIREPROOFING, PRIOR TO OR AFTER
INSTALLATION OF CEILING RUNNERS.
3. WHEN THE STEEL DECK IS COATED WITH FIREPROOFING, HILTI FIRESTOP JOINT SPRAY
SHALL OVERLAP THE WALL A MINIMUM 1/2" AND OVERLAP THE FIREPROOFING A MINIMUM 2"
ON BOTH SIDES OF GYPSUM WALL ASSEMBLY.
4. AS AN ALTERNATE TO CEILING RUNNER IN ITEM NO. 3, SLOTTED CEILING RUNNERS MAY BE
USED. CONSULT THE UL FIRE RESISTANCE DIRECTORY FOR APPROVED MANUFACTURERS.
HWD
2 of 2
-
UL/cUL SYSTEM NO. HW-D-0089
TOP OF WALL JOINT : GYPSUM WALL ASSEMBLY
Tulsa, Oklahoma USA (800) 879-8000
ASSEMBLY RATING = 1-HR. OR 2-HR.
CLASS II AND III MOVEMENT CAPABILITIES - 20% COMPRESSION OR EXTENSION)
L-RATING AT AMBIENT = LESS THAN 1 CFM / LIN FT
L-RATING AT 400°F = LESS THAN 1 CFM / LIN FT
0089s
Oct. 23, 2013