/ 1699
WL 8098 CFS-BL - Shaft wall (Z - frame) — page 928

Page text

Sheet
Drawing No.
HILTI, Inc.
Date
Scale
1. GYPSUM SHAFT WALL ASSEMBLY (UL/cUL CLASSIFIED U400, V400, OR W400 SERIES) (1-HR. OR 2-HR.
FIRE-RATING) (2-HR. SHOWN).
2. "C-T" OR "C-H" SHAPED STEEL STUDS (MINIMUM 2-1/2" WIDE x 1-1/2" DEEP, MIN. 25 GA.) SPACED
MAXIMUM 24" OC.
3. MINIMUM 1-3/4" x 5" (MIN. 24 GA.) STEEL ANGLE, HILTI L-SLEEVE, OR HILTI Z-FRAME CUT TO FIT ALL
FOUR SIDES OF OPENING. SLEEVE/ANGLE TO BE SECURED TO ONE SIDE OF WALL THROUGH THE
FLANGES WITH MINIMUM 1-1/2" LONG DRYWALL SCREWS (SPACED MAX. 8" OC) AROUND PERIMETER OF
OPENING.
4. ONE OR MORE OF THE FOLLOWING MAY BE INSTALLED WITHIN THE OPENING :
A. MAXIMUM 4" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER).
B. MAXIMUM 4" NOMINAL DIAMETER CAST OR DUCTILE IRON PIPE.
C. MAXIMUM 4" NOMINAL DIAMETER COPPER PIPE OR TUBING.
D. MAXIMUM 4" NOMINAL DIAMETER STEEL CONDUIT OR EMT.
5. [OPTIONAL] ONE OR MORE METALLIC PIPES MAY BE INSULATED WITH NOMINAL 3/4" OR 1" AB/PVC PIPE
INSULATION.
6. ONE MAXIMUM 2" DIAMETER CABLE BUNDLE CONSISTING OF ANY OF THE FOLLOWING :
A. MAXIMUM 25 PAIR NO. 24 AWG TELEPHONE CABLE WITH PVC JACKET.
B. MAXIMUM 7/C NO. 12 AWG COPPER CONDUCTOR POWER CABLE WITH PVC JACKET.
C. MAXIMUM 1/2" DIAMETER FIBER-OPTIC CABLE WITH PVC JACKET.
D. MAXIMUM 3/C NO. 8 AWG, WITH BARE ALUMINUM GROUND, STEEL METAL CLAD CABLE.
E. MAXIMUM 3/C (WITH GROUND) NO. 8 AWG NON-METALLIC SHEATHED CABLE (ROMEX) WITH PVC
JACKET.
F. TYPE R GU/59 COAXIAL CABLE WITH PVC JACKET.
G. MAXIMUM 4 PAIR NO. 22 AWG CAT 5 OR CAT 6 DATA CABLE.
7. HILTI CFS-BL FIRESTOP BLOCK (2" THICK x 8" WIDE x 5" DEEP, REFERENCE : FRONT VIEW) FIRMLY
PACKED WITHIN WALL, FLUSH WITH FINISHED SIDE OF WALL.
NOTES : 1. MAXIMUM SIZE OF OPENING = 22-3/4" x 10".
2. ANNULAR SPACE BETWEEN PENETRANTS AND BETWEEN PENETRANTS AND PERIPHERY
OF OPENING = MINIMUM 1/2".
3. APPLY HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT OR HILTI CP 618 FIRESTOP
PUTTY STICK INTO ANY VOID THAT MAY EXIST AROUND PENETRANTS, INTO INTERSTICES
OF CABLES, OR BETWEEN FIRESTOP BLOCKS TO MAXIMUM EXTENT POSSIBLE.
WL
UMVU~
2 of 2
-
Dec. 21, 2012
UL/cUL SYSTEM NO. W-L-8098
F-RATING = 1-HR. OR 2-HR.
T-RATING = 0-HR., 1/2-HR., OR 3/4-HR.
tiUMVU~KNOONNO
MULTIPLE PENETRATING ITEMS THROUGH GYPSUM SHAFT WALL ASSEMBLY
Tulsa, Oklahoma USA (800) 879-8000