UL/cUL SYSTEM NO. W-L-8086
F-RATING = 1-HR. OR 2-HR.
T-RATING = 0-HR., 1/2-HR., 3/4-HR., 1-HR., 1 3/4-HR., OR 2-HR.
MULTIPLE PENETRATING ITEMS THROUGH GYPSUM WALL ASSEMBLY
Tulsa, Oklahoma USA (800) 879-8000
NOTES : 1. MAXIMUM DIAMETER OF OPENING = 2-1/2" (FOR 2" DEVICE) OR 4-1/2" (FOR 4" DEVICE).
2. ANNULAR SPACE BETWEEN DEVICE AND PERIPHERY OF OPENING = MINIMUM 0".
3. CABLES MAY REPRESENT 0% TO 100% VISUAL FILL OF DEVICE.
4. [OPTIONAL] AS AN ALTERNATE TO SMOKE GASKET, MINIMUM 1/2" DEPTH HILTI FS-ONE
INTUMESCENT FIRESTOP SEALANT OR HILTI CP 606 FLEXIBLE FIRESTOP SEALANT FLUSH WITH
BOTH SURFACES OF WALL WITH AN ADDITIONAL 1/4" BEAD APPLIED AROUND PERIPHERY OF
DEVICE PRIOR TO SECURING DEVICE FLANGES.
1. GYPSUM WALL ASSEMBLY (UL/cUL CLASSIFIED U300, U400 OR V400 SERIES) (1-HR. OR 2-HR.
FIRE-RATING) (2-HR. SHOWN) TO INCLUDE THE FOLLOWING CONSTRUCTION FEATURES :
A. [NOT SHOWN] WOOD STUDS TO CONSIST OF NOMINAL 2" x 4" LUMBER (SPACED MAXIMUM 16" OC).
STEEL STUDS TO BE MINIMUM 3-1/2" WIDE (SPACED MAXIMUM 24" OC).
B. NOMINAL 5/8" THICK GYPSUM WALLBOARD. TYPE, NUMBER OF LAYERS, AND SHEET ORIENTATION
AS SPECIFIED IN THE INDIVIDUAL UL DESIGN.
2. CABLE BUNDLE TO BE A COMBINATION OF ANY OF THE FOLLOWING :
A. MAXIMUM 100 PAIR NO. 24 AWG TELEPHONE CABLE WITH PVC JACKET.
B. MAXIMUM 7/C NO. 12 AWG COPPER CONDUCTOR CONTROL CABLE WITH PVC OR XLPE JACKET AND
INSULATION.
C. MAXIMUM 4/0 AWG TYPE RHH GROUND CABLE.
D. MAXIMUM 4 PAIR NO. 22 AWG CAT 6 COMPUTER CABLE.
E. MAXIMUM RG 6/U COAXIAL CABLE.
F. MAXIMUM 1/2" DIAMETER FIBER-OPTIC CABLE (24 FIBER) WITH PVC OR PE JACKET AND INSULATION.
G. MAXIMUM 2/C NO. 22 AWG SHIELDED PRINTER CABLE WITH PVC JACKET.
H. MAXIMUM 2/C NO. 18 AWG POWER OR NON-POWER LIMITED FIRE ALARM CABLE WITH OR WITHOUT
METAL JACKET (MANUFACTURED BY AFC CABLE SYSTEMS, INC.).
I. MAXIMUM 1/4" DIAMETER S-VIDEO CABLE CONSISTING OF TWO MAXIMUM 24 AWG 75 OHM COAX OR
TWISTED PAIR CABLE WITH PE INSULATION AND PVC JACKET.
J. MAXIMUM 3/C NO. 12 AWG METAL CLAD CABLE.
K. ANY CABLES, METAL-CLAD CABLES, OR ARMORED CABLES CURRENTLY LISTED UNDER THE
THROUGH PENETRATING PRODUCTS CATEGORY.
3. ONE OF THE FOLLOWING PENETRATING ITEMS MAY BE INSTALLED :
A. MAXIMUM 2" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 5 OR HEAVIER).
B. MAXIMUM 2" NOMINAL DIAMETER CAST OR DUCTILE IRON PIPE.
C. MAXIMUM 2" NOMINAL DIAMETER COPPER PIPE OR TUBING.
D. MAXIMUM 2" NOMINAL DIAMETER STEEL CONDUIT OR EMT.
E. MAXIMUM 1" NOMINAL DIAMETER FLEXIBLE STEEL CONDUIT.
4. HILTI CP 653 SPEED SLEEVE (2" OR 4") SLID INTO AND CENTERED WITHIN WALL. DEVICE FLANGES SPUN
CLOCKWISE ONTO DEVICE THREADS, BUTTING TIGHTLY TO BOTH SIDES OF WALL.