Page text
Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
NOTES : 1. MAXIMUM AREA OF OPENING = 144 SQUARE INCHES WITH MAXIMUM DIMENSION OF 12".
2. ANNULAR SPACE BETWEEN PIPE AND PERIPHERY OF OPENING = MINIMUM 0", MAXIMUM 4".
3. ANNULAR SPACE BETWEEN CABLE BUNDLE AND PERIPHERY OF OPENING = MINIMUM 0",
MAXIMUM 6".
4. ANNULAR SPACE BETWEEN PENETRANTS = MINIMUM 2", MAXIMUM 4".
5. INSTALL HILTI FS-ONE FIRESTOP SEALANT IN ANY VOID THAT MAY EXIST (AROUND CABLES,
OR PIPE PENETRANT).
6. [NOT SHOWN] ATTACH A STEEL WIRE MESH (NOMINAL 2" SQUARES, NO. 16 SWG) WITH 1/4"
DIAMETER x 4-3/16" LONG STEEL CONCRETE ANCHORS AND 1-1/2" DIAMETER FENDER
WASHERS (SPACED MAXIMUM 8" C/C) ON BOTH SIDES OF WALL ASSEMBLY. STEEL WIRE
MESH CUT TO FIT CONTOUR OF THE PENETRANT AND OVERLAP MINIMUM 3" BEYOND THE
PERIPHERY OF THE OPENING.
1. PRECAST AUTOCLAVED AERATED CONCRETE WALL ASSEMBLY (UL DESIGN NO. U916 OR U917)
(4-HR. FIRE-RATING).
2. PENETRATING ITEM TO BE ANY ONE OF THE FOLLOWING :
A. MAXIMUM 6" NOMINAL DIAMETER STEEL PIPE (SCH. 10 OR HEAVIER).
B. MAXIMUM 6" NOMINAL DIAMETER CAST IRON PIPE.
C. MAXIMUM 6" NOMINAL DIAMETER COPPER PIPE.
D. MAXIMUM 6" NOMINAL DIAMETER STEEL CONDUIT.
E. MAXIMUM 4" NOMINAL DIAMETER EMT.
3. MAXIMUM 4" DIAMETER CABLE BUNDLE TO INCLUDE ANY OF THE FOLLOWING :
A. 300 PAIR NO. 24 AWG TELEPHONE CABLE WITH PVC JACKET.
B. 7/C NO. 12 AWG CABLE WITH PVC JACKET.
4. HILTI CFS-BL FIRESTOP BLOCK OR HILTI FS 657 FIRE BLOCK (2" THICK x 5" WIDE x 8" DEEP,
REFERENCE : FRONT VIEW).
WJ
8009c
1 of 1
5/64" = 1"
Mar. 21, 2012
UL/cUL SYSTEM NO. W-J-8009
F-RATING = 4-HR.
T-RATING = 0-HR.
WJ8009c.032112
MULTIPLE PENETRATIONS THROUGH CONCRETE WALL
A
SECTION A-A
FRONT VIEW
A
1
2
3
4