FA 8023 - Steel / ENT / Cables — page 853

Page text

Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
NOTES : 1. FOR CONCRETE FLOOR OVER METAL DECKING APPLICATIONS, A METAL DECK
ADAPTER KIT IS REQUIRED.
2. ANNULAR SPACE BETWEEN BUNDLE AND DEVICE = MINIMUM 1/2", MAXIMUM 2".
3. ENT NOT APPLICABLE FOR USE IN CANADA.
1. CONCRETE FLOOR OR WALL ASSEMBLY (3-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR OR WALL (MINIMUM 4-1/2" THICK).
B. STEEL FLOOR UNIT/FLOOR ASSEMBLY - LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR
(MINIMUM 4-1/2" THICK) OVER METAL DECKING.
2. PENETRATING ITEMS TO BE ANY BUNDLED COMBINATION OF THE FOLLOWING :
A. MAXIMUM 2" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER) (MAX. QTY. = 1).
B. MAXIMUM 2" NOMINAL DIAMETER ENT (MAX. QTY. = 2) (SEE NOTE NO. 3 BELOW).
C. MAXIMUM 2" DIAMETER CABLE BUNDLE CONSISTING OF MAXIMUM 7/C NO. 12 AWG CABLE
AND/OR MAXIMUM 25 PAIR NO. 24 AWG TELEPHONE CABLE.
3. HILTI CP 680-P [2", 3", 4" OR 6"] CAST-IN FIRESTOP DEVICE CAST OR GROUTED INTO CONCRETE
FLOOR.
4. MINIMUM 2" THICKNESS MINERAL WOOL (MIN. 4 PCF DENSITY) TIGHTLY PACKED AND FLUSH WITH
TOP OF FIRESTOP DEVICE.
FA
8023c
1 of 1
5/32" = 1"
Dec. 11, 2013
UL/cUL SYSTEM NO. F-A-8023
F-RATING = 3-HR.
T-RATING = 0-HR.
FA8023c.121113
MULTIPLE PENETRANTS THROUGH CONCRETE FLOOR OR
CONCRETE OVER METAL DECKING
A
A
SECTION A-A
TOP VIEW
1
2
3
4