NOTES : 1. MAXIMUM SIZE OF OPENING = 5" x 3" [OR MAXIMUM 3" DIAMETER].
2. ANNULAR SPACE = MINIMUM 1/8", MAXIMUM 7/8".
3. PENETRANT MAY BE INSTALLED AT AN ANGLE NOT GREATER THAN 45° FROM
PERPENDICULAR.
4. WHEN HILTI CP 606 FLEXIBLE FIRESTOP SEALANT IS USED ON AN ANGLED PENETRANT,
FIRMLY PACK 1/2" THICKNESS OF MINERAL WOOL (MIN. 4 PCF DENSITY) INTO OPENING
AS A PERMANENT FORM.
1. CONCRETE WALL ASSEMBLY (2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL (MINIMUM 5" THICK).
B. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
2. PENETRATING ITEM TO BE ONE OF THE FOLLOWING :
A. MAXIMUM 1-5/8" x 1-5/8" GALVANIZED OR PAINTED STEEL CHANNEL STRUT (MINIMUM 0.105" THICK).
B. MAXIMUM 3-1/4" x 1-5/8" GALVANIZED OR PAINTED STEEL "H" STRUT (MINIMUM 0.105" THICK).
C. MAXIMUM 3/8" DIAMETER UNJACKETED GALVANIZED STEEL CABLE.
D. MAXIMUM 1" DIAMETER GALVANIZED THREADED STEEL ROD.
E. MAXIMUM 2" x 2" x 1/8" THICK STEEL ANGLE.
3. MINIMUM 5/8" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT OR HILTI CP 606 FLEXIBLE
FIRESTOP SEALANT.
WJ
TNOP~
1 of 1
5/32" = 1"
Oct. 07, 2013
UL/cUL SYSTEM NO. W-J-7123
F-RATING = 2-HR.
T-RATING = 0-HR.
WJ7123a.100713
MECHANICAL SUPPORT MEMBER THROUGH CONCRETE WALL
OR BLOCK WALL ASSEMBLY
A
SECTION A-A
FRONT VIEW