WL 5143 - (1 1/2") - 3/4" AB/PVC — page 687

Page text

Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (918) 252-6000
Date
Scale
FRONT VIEW
A
A
SECTION A-A
NOTES : 1. MAXIMUM DIAMETER OF OPENING = 4".
2. ANNULAR SPACE = MINIMUM 1/4", MAXIMUM 1-1/8".
3. AS AN ALTERNATE TO THE ABOVE SHAFT WALL ASSEMBLY, A 1 OR 2-HR. GYPSUM WALL
ASSEMBLY MAY BE USED (U300, U400 OR V400 SERIES). STEEL STUDS TO BE MINIMUM 2-1/2"
WIDE. WOOD STUDS TO CONSIST OF NOMINAL 2 x 4 LUMBER.
4. WHEN SYSTEM IS INSTALLED IN A STANDARD WALL ASSEMBLY, MINERAL WOOL SHOULD
BE INSTALLED FLUSH WITH EITHER SIDE OF WALL AND RECESSED FROM OTHER SIDE TO
ACCOMMODATE SEALANT.
1. GYPSUM SHAFT WALL ASSEMBLY (UL/ULC CLASSIFIED U400 SERIES) (1-HR. OR 2-HR. FIRE-RATING).
2. "C-T" SHAPED STEEL STUDS (1-5/8" WIDE x 2-1/2" DEEP, MINIMUM 25 GA.) SPACED MAXIMUM 24" C/C.
3. MAXIMUM 1" NOMINAL DIAMETER COPPER PIPE.
4. NOMINAL 3/4" THICK AB/PVC FLEXIBLE FOAM PIPE INSULATION.
5. MAXIMUM 4" DIAMETER SHEET METAL SLEEVE (MINIMUM 28 GA.) OR NO. 8 STEEL WIRE MESH HAVING
MINIMUM 1" OVERLAP ALONG LONGITUDINAL SEAM.
6. MINIMUM 1-5/8" OR 2-1/4" THICKNESS MINERAL WOOL (MINIMUM 4 PCF DENSITY) TIGHTLY PACKED AND
RECESSED ON ONE SIDE OF WALL FOR 1-HR. OR 2-HR. FIRE-RATED WALLS RESPECTIVELY.
7. MINIMUM 1-1/2" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT.
WL
5143c
1 of 1
3/16" = 1"
Sep. 08, 2005
UL/cUL SYSTEM NO. W-L-5143
F-RATING = 1 AND 2-HR.
T-RATING = 1/2-HR.
WL5143c.090805