FE 5013 (1/2'' - 1'') Glass-fiber membrane ceiling — page 660

Page text

Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
A
A
NOTES : 1. DIAMETER OF OPENING TO BE 1-1/2" LARGER THAN OUTSIDE
DIAMETER OF INSULATED METAL PIPE.
2. ANNULAR SPACE = MINIMUM 1/2", MAXIMUM 1".
1. CONCRETE AND STEEL JOIST FLOOR/CEILING ASSEMBLY (UL/cUL CLASSIFIED G500 SERIES)
(1-HR. FIRE-RATING).
2. PENETRATING ITEM TO BE ONE OF THE FOLLOWING :
A. MAXIMUM 2" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER).
B. MAXIMUM 2" NOMINAL DIAMETER COPPER PIPE.
3. NOMINAL 1-1/2" THICKNESS GLASS-FIBER PIPE INSULATION.
4. MINIMUM 3/4" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT.
5. MINIMUM 5/8" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT.
FE
5013a
1 of 1
9/64" = 1"
Dec. 11, 2013
UL/cUL SYSTEM NO. F-E-5013
F-RATING = 1-HR.
T-RATING = 1-HR.
FE5013a.121113
INSULATED METAL PIPE THROUGH CONCRETE FLOOR/CEILING ASSEMBLY
1
2
3
4
5
SECTION A-A
BOTTOM VIEW