Page text
Sheet
Drawing No.
HILTI, Inc.
Date
Scale
NOTES : 1. FOR CONCRETE FLOOR OVER METAL DECKING APPLICATIONS, A METAL DECK ADAPTER
KIT IS REQUIRED.
2. WHEN USING A NOMINAL 1" DIAMETER PIPE WITH 1-1/2" THICK INSULATION IN A 4" DEVICE,
TIGHTLY PACK A MINIMUM 2" THICKNESS OF MINERAL WOOL (MINIMUM 4 PCF DENSITY)
FLUSH WITH THE TOP OF FIRESTOP DEVICE.
1. CONCRETE FLOOR ASSEMBLY (2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR (MINIMUM 2-1/2" THICK).
B. STEEL FLOOR UNIT/FLOOR ASSEMBLY - LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR
(MINIMUM 2-1/2" THICK) OVER METAL DECKING.
2. PENETRATING ITEM TO BE ONE OF THE FOLLOWING :
A. MAXIMUM 4" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER).
B. MAXIMUM 4" NOMINAL DIAMETER COPPER PIPE OR TUBING.
3. NOMINAL 1", 1-1/2" OR 2" THICK GLASS-FIBER PIPE INSULATION.
4. HILTI CP 680-M OR CP 680-P CAST-IN FIRESTOP DEVICE, CAST OR GROUTED INTO CONCRETE FLOOR
(SEE TABLE BELOW).
FA
5017g
1 of 1
7/64" = 1"
Sep. 18, 2013
UL/cUL SYSTEM NO. F-A-5017
F-RATING = 2-HR.
T-RATING = 3/4-HR. OR 1-HR.
FA5017g.091813
INSUALTED METAL PIPE THROUGH CONCRETE FLOOR OR
CONCRETE OVER METAL DECKING
A
A
SECTION A-A
TOP VIEW
Tulsa, Oklahoma USA (800) 879-8000
NOMINAL PIPE DIAMETER
GLASS-FIBER THICKNESS
PRODUCT DESCRIPTION
1/2"
1"
CP 680-M 2" OR CP 680-P 2"
1"
1"
CP 680-M 3" OR CP 680-P 3"
1" (SEE NOTE 2)
1-1/2" (SEE NOTE 2)
CP 680-M 4" OR CP 680-P 4"
2"
1"
CP 680-M 4" OR CP 680-P 4"
2"
2"
CP 680-M 6" OR CP 680-P 6"
4"
1"
CP 680-M 6" OR CP 680-P 6"
1
2
3
4
MAX. 2"