Page text
Sheet
Drawing No.
HILTI, Inc.
Date
Scale
NOTES : 1. FOR CONCRETE FLOOR OVER METAL DECKING APPLICATIONS, A METAL DECK ADAPTER
KIT IS REQUIRED.
2. WHEN USING A NOMINAL 1" DIAMETER PIPE WITH 1" THICK INSULATION IN A 4" DEVICE,
TIGHTLY PACK 2" THICKNESS OF MINERAL WOOL (MINIMUM 4 PCF DENSITY) FLUSH WITH
THE TOP OF DEVICE.
1. CONCRETE FLOOR ASSEMBLY (2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR (MINIMUM 2-1/2" THICK).
B. STEEL FLOOR UNIT/FLOOR ASSEMBLY - LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE
FLOOR (MINIMUM 2-1/2" THICK) OVER METAL DECKING.
2. PENETRATING ITEM TO BE ONE OF THE FOLLOWING (SEE TABLE BELOW) :
A. MAXIMUM 4" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER).
B. MAXIMUM 4" NOMINAL DIAMETER COPPER PIPE OR TUBING.
3. NOMINAL 3/4" OR 1" THICK AB/PVC FLEXIBLE FOAM PIPE INSULATION.
4. HILTI CP 680-M OR CP 680-P CAST-IN FIRESTOP CAST OR GROUTED INTO CONCRETE FLOOR
(SEE TABLE BELOW).
FA
5015g
1 of 1
3/32" = 1"
Oct. 07, 2013
UL/cUL SYSTEM NO. F-A-5015
F-RATING = 2-HR.
T-RATING = 1/2-HR. OR 3/4-HR.
FA5015g.100713
INSULATED METAL PIPE THROUGH CONCRETE FLOOR OR
CONCRETE OVER METAL DECKING
A
A
SECTION A-A
TOP VIEW
Tulsa, Oklahoma USA (800) 879-8000
NOMINAL PIPE DIAMETER
AB/PVC THICKNESS
PRODUCT DESCRIPTION
1/2"
1"
CP 680-M 2" OR CP 680-P 2"
1"
3/4"
CP 680-P 3"
1"
1"
CP 680-M 3" OR CP 680-P 3"
1" (SEE NOTE NO. 2)
1"
CP 680-M 4"
2"
1"
CP 680-M 4" OR CP 680-P 4"
2"
3/4" OR 1"
CP 680-M 4" OR CP 680-P 4"
4"
3/4" OR 1"
CP 680-M 6" OR CP 680-P 6"
MAX. 2"
1
2
3
4