/ 1699
CAJ 4054 - (5") Max 32" x 7" — page 550

Page text

Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
A
A
NOTES : 1. MAXIMUM AREA OF OPENING = 224 SQ. IN. WITH A MAXIMUM DIMENSION OF 32".
2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 5".
3. MAXIMUM AREA OF CABLES SHALL BE 45% OF CROSS-SECTIONAL AREA OF CABLE TRAY.
4. [OPTIONAL - NOT SHOWN] HILTI CFS-BL FIRESTOP BLOCKS OR HILTI FS 657 FIRE BLOCKS
MAY BE APPLIED IN A SINGLE LAYER ABOVE CABLES WITHIN CABLE TRAY (2" THICK x 8"
WIDE x 5" DEEP) FIRMLY PACKED WITHIN OPENING.
1. CONCRETE FLOOR OR WALL ASSEMBLY (2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR OR WALL (MINIMUM 4-1/2").
B. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
2. MAXIMUM 24" x 4" ALUMINUM OPEN LADDER CABLE TRAY.
3. CABLES TO A COMBINATION OF ANY OF THE FOLLOWING (SEE NOTE NO. 3 BELOW) :
A. MAXIMUM 300 PAIR NO. 24 AWG TELEPHONE CABLE.
B. MAXIMUM 500 KCMIL SINGLE CONDUCTOR POWER CABLE.
C. MAXIMUM 3/8" DIAMETER FIBER-OPTIC CABLE.
D. MAXIMUM 3/C NO. 12 AWG METAL-CLAD CABLE.
4. MINIMUM 5" DEPTH HILTI CP 620 FIRE FOAM EXTENDING ABOVE THE TOP SURFACE OF THE FLOOR OR
BOTH SURFACES OF WALL AND OVERLAPPING THE CONCRETE 1/2" ON ALL SIDES OF OPENING.
CAJ
4054b
1 of 1
1/8" = 1"
Jan. 11, 2012
UL/cUL SYSTEM NO. C-AJ-4054
F-RATING = 2-HR.
T-RATING = 0-HR.
CAJ4054b.011112
CABLE TRAY THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL ASSEMBLY
1
2
3
4
SECTION A-A
TOP VIEW