/ 1699
WL-3395 Gang plate — page 527

Page text

Sheet
Drawing No.
HILTI, Inc.
Date
Scale
WL
3395c
1 of 3
3/32" = 1"
Aug. 28, 2013
UL/cUL SYSTEM NO. W-L-3395
F-RATING = 1-HR. OR 2-HR.
T-RATING = 1/4-HR.
L-RATING = SEE TABLES BELOW
WL3395c.082813
MULTIPLE CABLE BUNDLES THROUGH GYPSUM WALL ASSEMBLY
A
SECTION A-A
FRONT VIEW
Tulsa, Oklahoma USA (800) 879-8000
A
1. GYPSUM WALL ASSEMBLY (UL/cUL CLASSIFIED U400, V400, OR W400 SERIES) (1-HR. OR 2-HR.
FIRE-RATING) (2-HR. SHOWN) TO INCLUDE THE FOLLOWING CONSTRUCTION FEATURES :
A. [NOT SHOWN] STEEL STUDS TO BE MINIMUM 3-1/2" WIDE (SPACED MAXIMUM 24" OC).
B. NOMINAL 5/8" THICK GYPSUM WALLBOARD. TYPE, NUMBER OF LAYERS, AND SHEET ORIENTATION
AS SPECIFIED IN THE INDIVIDUAL UL DESIGN.
2. HILTI CFS-SL GP FIRESTOP GANGPLATE (16" OR 24") ORIENTED VERTICALLY OR HORIZONTALLY AND
SECURED TO THE FACE OF THE WALL OR DIRECTLY AGAINST STUDS PRIOR TO INSTALLATION OF
GYPSUM BOARD (SEE MAXIMUM SIZE OF OPENING TABLE FOR INSTALLATION OPTIONS). IN 1-HR.
WALLS, BLANK DOUBLE STACKED GANGPLATES (NO CABLES) ARE LIMITED TO HORIZONTAL
INSTALLATION WITH FASTENERS INTO WALL STUDS.
1
2
3
5
6
3