WL 3065aa — page 481

Page text

Sheet
Drawing No.
HILTI, Inc.
Date
Scale
WL
1 of 2
7/64" = 1"
UL/cUL SYSTEM NO. W-L-3065
CABLE BUNDLE THROUGH GYPSUM WALL ASSEMBLY
A
SECTION A-A
FRONT VIEW
Tulsa, Oklahoma USA (800) 879-8000
B
SECTION B-B
FRONT VIEW
F-RATING = 1-HR. OR 2-HR.
T-RATING = 0-HR. OR 3/4-HR.
L-RATING AT AMBIENT = 15 CFM / SQ FT
L-RATING AT 400° F = 8 CFM / SQ FT
3065aa
1. GYPSUM WALL ASSEMBLY (UL/cUL CLASSIFIED U300, U400, OR V400) (1-HR. OR 2-HR. FIRE-RATING)
(2-HR. SHOWN).
2. [NOT SHOWN] WOOD STUDS TO CONSIST OF NOMINAL 2" x 4" LUMBER. STEEL STUDS TO BE
MINIMUM 2-1/2" WIDE.
3. [OPTIONAL] MAXIMUM 4" NOMINAL DIAMETER EMT, STEEL PIPE (SCHEDULE 5 OR HEAVIER) OR 28 GA.
GALVANIZED STEEL SLEEVE (SEE NOTE NO. 6 BELOW).
Mar. 13, 2014
WL3065aa.031314
A
B
1
2
3
4
6
5
1
2
3
4
6
5
5
MAXIMUM 18"
MAXIMUM 18"