Page text
Sheet
Drawing No.
HILTI, Inc.
Date
Scale
2. CABLE BUNDLE TO BE A COMBINATION OF ANY OF THE FOLLOWING :
A. MAXIMUM 100 PAIR NO. 24 AWG TELEPHONE CABLE WITH PVC JACKET.
B. MAXIMUM 7/C NO. 12 AWG COPPER CONDUCTOR CONTROL CABLE WITH PVC OR XLPE JACKET AND
INSULATION.
C. MAXIMUM 4/0 AWG TYPE RHH GROUND CABLE.
D. MAXIMUM 4 PAIR NO. 22 AWG CAT 5 OR CAT 6 COMPUTER CABLE.
E. MAXIMUM RG 6/U COAXIAL CABLE.
F. MAXIMUM 1/2" DIAMETER FIBER-OPTIC CABLE (24 FIBER) WITH PVC OR PE JACKET AND INSULATION.
G. MAXIMUM 20/C NO. 22 AWG SHIELDED PRINTER CABLE WITH PVC JACKET.
H. MAXIMUM 2/C NO. 18 AWG POWER OR NON-POWER LIMITED FIRE ALARM CABLE WITH OR WITHOUT
METAL JACKET (MANUFACTURED BY AFC CABLE SYSTEMS, INC.).
I. MAXIMUM 1/4" DIAMETER S-VIDEO CABLE CONSISTING OF TWO MAXIMUM 24 AWG 75 OHM COAX OR
TWISTED PAIR CABLE WITH PE INSULATION AND PVC JACKET.
3. HILTI CP 653 SPEED SLEEVE (2" OR 4") SLID INTO AND CENTERED WITHIN WALL. DEVICE FLANGES SPUN
CLOCKWISE ONTO DEVICE THREADS OVER SMOKE GASKET, BUTTING TIGHTLY TO BOTH SIDES OF WALL.
4. SECURE DEVICE FLANGES TO BOTH SIDES OF WALL WITH TWO MINIMUM 1-1/2" LONG MASONRY
SCREWS OR ANCHORS.
2 of 2
-
Tulsa, Oklahoma USA (800) 879-8000
WJ
CABLE BUNDLE THROUGH CONCRETE OR BLOCK WALL ASSEMBLY
NOTES : 1. MAXIMUM DIAMETER OF OPENING = 3" (FOR 2" DEVICE) OR 5" (FOR 4" DEVICE).
2. CABLES MAY REPRESENT 0% TO 100% VISUAL FILL OF DEVICE.
3. ANNULAR SPACE BETWEEN DEVICE AND PERIPHERY OF OPENING = MINIMUM 0".
4. L-RATING DOES NOT APPLY WHEN HILTI CP 618 FIRESTOP PUTTY IS USED.
5. [OPTIONAL] INNER FABRIC MAY REMAIN OPEN WHEN L-RATING IS NOT REQUIRED.
6. [OPTIONAL] AS AN ALTERNATE TO SMOKE GASKET, MINIMUM 5/8" DEPTH HILTI FS-ONE
INTUMESCENT FIRESTOP SEALANT, HILTI CP 606 FLEXIBLE FIRESTOP SEALANT, OR
HILTI CP 618 FIRESTOP PUTTY STICK FLUSH WITH BOTH SURFACES OF WALL WITH AN
ADDITIONAL 1/4" BEAD OF FIRESTOP SEALANT (NOT REQUIRED FOR PUTTY) APPLIED
AT POINT OF CONTACT.
UL/cUL SYSTEM NO. W-J-3168
MAX
CABLE
FILL
CABLE TYPE
L-RATING, CFM/SQ FT
L-RATING, CFM
AMBIENT
400°F
AMBIENT
400°F
SEALANT
GASKET
SEALANT
GASKET
SEALANT
GASKET
SEALANT
GASKET
0% FILL
-
LESS THAN 1
1
LESS THAN 1
2.7
LESS THAN 1
LESS THAN 1
LESS THAN 1
LESS THAN 1
100%
ITEM 2D ONLY
4.9
4.9
1.3
3.5
LESS THAN 1
LESS THAN 1
LESS THAN 1
LESS THAN 1
100%
ANY CABLES
(ITEM 2) IN ANY
COMBINATION
9.2
9.2
9.6
NNKU
1.2
1.2
1.3
1.6
3168d
Aug. 22, 2014
F-RATING = 2-HR.
T-RATING = 0-HR., 1/2-HR., AND 1-HR.
L-RATING AT AMBIENT = SEE TABLE
L-RATING AT 400°F = SEE TABLE
WJ3168d.082214