NOTES : 1. MAXIMUM DIAMETER OF OPENING FOR 1", 2", AND 4" SLEEVES ARE 1-1/4", 2-7/16", AND
4-1/2" RESPECTIVELY.
2. CABLES TO FILL MINIMUM 8" TO MAXIMUM 48% OF CROSS-SECTIONAL AREA OF SLEEVE.
1. CONCRETE WALL ASSEMBLY (2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL (MINIMUM 6" THICK).
B. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
2. CABLE BUNDLE TO BE ANY COMBINATION OF THE FOLLOWING :
A. MAXIMUM 200 PAIR NO. 24 AWG (OR SMALLER) COPPER CONDUCTOR CABLE WITH PVC JACKET.
B. MAXIMUM 750 KCMIL POWER CABLE WITH PVC JACKET.
C. MAXIMUM 3/C NO. 2/0 AWG (OR SMALLER) ALUMINUM OR COPPER CONDUCTOR SERVICE ENTRANCE
CABLE WITH PVC JACKET.
D. MAXIMUM 3/C NO. 8 AWG (OR SMALLER) NONMETALLIC SHEATHED (ROMEX) CABLE WITH COPPER
CONDUCTORS AND PVC JACKET.
E. MAXIMUM 7/C NO. 12 AWG (OR SMALLER) POWER AND CONTROL CABLES WITH XLPE OR PVC
JACKET.
F. MAXIMUM RG6/U (OR SMALLER) COAXIAL CABLE WITH FLUORINATED ETHYLENE JACKET.
G. MAXIMUM 62.5/48 FIBER-OPTIC CABLE WITH PVC JACKET.
H. MAXIMUM 4 PAIR NO. 24 AWG (OR SMALLER) CAT 5 CABLE WITH HYLAR JACKET.
3. SMOOTH SLEEVE (1", 2", AND 4" SIZES) MANUFACTURED BY UNIQUE FIRE STOP PRODUCTS, INC. AND
INSTALLED PER ACCOMPANYING INSTALLATION INSTRUCTIONS.
4. MINIMUM 1" DEPTH HILTI CP 618 FIRESTOP PUTTY STICK.
WJ
3109a
1 of 1
1/8" = 1"
Feb. 29, 2012
UL/cUL SYSTEM NO. W-J-3109
F-RATING = 2-HR.
T-RATING = 0-HR.
WJ3109a.022912
CABLE BUNDLE THROUGH "UNIQUE FIRE STOP SLEEVE" IN CONCRETE WALL OR
BLOCK WALL
A
SECTION A-A
FRONT VIEW