/ 1699
WJ 3060 - (5/8") Various — page 443

Page text

Sheet
Drawing No.
HILTI, Inc.
Date
Scale
1. CONCRETE WALL ASSEMBLY (1-HR. OR 2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL (MINIMUM 4-3/4" THICK, FOR A 1-HR.
FIRE-RATING).
B. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL (MINIMUM 6" THICK, FOR A 2-HR.
FIRE-RATING).
C. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL ASSEMBLY.
2. [OPTIONAL] MAXIMUM 4" NOMINAL DIAMETER EMT, STEEL PIPE (SCHEDULE 5 OR HEAVIER) OR 28 GA.
GALVANIZED STEEL SLEEVE, CAST INTO WALL FLUSH WITH WALL SURFACES (SEE NOTE NO. 5 BELOW).
3. CABLE BUNDLE TO CONSIST OF ANY COMBINATION OF THE FOLLOWING :
A. MAXIMUM 7/C NO. 12 AWG POWER CABLE WITH PVC JACKET.
B. MAXIMUM 25 PAIR NO. 24 AWG TELEPHONE CABLE WITH PVC JACKET.
C. MAXIMUM RG 59 OR MAXIMUM RG 6/U COAXIAL CABLE WITH PVC JACKET.
D. MAXIMUM 3/C NO. 8 AWG METAL-CLAD CABLE.
E. MAXIMUM 5/8 DIAMETER FIBER-OPTIC CABLE WITH PVC JACKET.
F. MAXIMUM 4 PAIR NO. 22 AWG CAT 5 OR CAT 6 CABLE.
G. ANY CABLES, METAL-CLAD OR ARMORED CABLE, CURRENTLY UL CLASSIFIED UNDER THE
THROUGH PENETRANTS PRODUCTS CATEGORY.
4. MINIMUM 5/8" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT, CP 601S ELASTOMERIC
FIRESTOP SEALANT, CP 606 FLEXIBLE FIRESTOP SEALANT, HILTI CFS-S SIL GG FIRESTOP SILICONE
SEALANT, OR CP 618 FIRESTOP PUTTY STICK.
5. MINIMUM 1/2" BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT, CP 601S ELASTOMERIC FIRESTOP
SEALANT, CP 606 FLEXIBLE FIRESTOP SEALANT, HILTI CFS-S SIL GG FIRESTOP SILICONE SEALANT, OR
CP 618 FIRESTOP PUTTY STICK APPLIED AT WALL/SLEEVE INTERFACE WHEN STEEL SLEEVE EXTENDS
BEYOND ONE OR BOTH SIDES OF WALL.
NOTES : 1. MAXIMUM DIAMETER OF OPENING WITH SLEEVE = 5-1/2".
2. MAXIMUM DIAMETER OF OPENING WITHOUT SLEEVE = 4".
3. ANNULAR SPACE = MINIMUM 0", MAXIMUM 1".
4. CABLES TO FILL MAXIMUM 45% OF CROSS-SECTIONAL AREA OF OPENING.
5. WHEN SCHEDULE 5 STEEL PIPE OR EMT IS USED, SLEEVE MAY EXTEND UP TO 18"
BEYOND WALL SURFACES. AS AN OPTION, SLEEVE MAY BE CONTINUOUS ON ONE
SIDE OF WALL ASSEMBLY.
6. WHEN SLEEVE IS CONTINUOUS ON ONE SIDE OF WALL, THE CABLE FILL MAY BE 0%
TO 45% AND THE MAXIMUM ANNULAR SPACE IS NOT LIMITED.
7. [OPTIONAL - NOT SHOWN] MINERAL WOOL (MIN. 4 PCF DENSITY) TIGHTLY PACKED
AND RECESSED TO ACCOMMODATE FIRESTOP SEALANT OR PUTTY MAY BE USED
AS BACKING MATERIAL.
WJ
2 of 2
-
UL/cUL SYSTEM NO. W-J-3060
F-RATING = 1-HR. OR 2-HR.
T-RATING = 0-HR.
L-RATING AT AMBIENT = 15 CFM / SQ FT
L-RATING AT 400° F = 8 CFM / SQ FT
CABLE BUNDLE THROUGH CONCRETE WALL OR BLOCK WALL ASSEMBLY
Tulsa, Oklahoma USA (800) 879-8000
3060k
Mar. 13, 2014
WJ3060k.031314