1. CONCRETE FLOOR ASSEMBLY (3-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR (MINIMUM 4-1/2" THICK).
B. STEEL FLOOR UNIT/FLOOR ASSEMBLY - LIGHTWEIGHT OR NORMAL WEIGHT
CONCRETE FLOOR (MINIMUM 4-1/2" THICK) OVER METAL DECKING.
2. CABLE BUNDLE CONSISTING OF ANY OF THE FOLLOWING :
A. MAXIMUM 300 PAIR NO. 24 AWG TELEPHONE CABLE WITH PVC JACKET.
B. MAXIMUM 750 KCMIL POWER CABLE WITH PVC JACKET.
C. MAXIMUM 7/C NO. 12 AWG POWER CABLE WITH PVC JACKET.
D. MAXIMUM (24 FIBER) 1/2" DIAMETER FIBER-OPTIC CABLE.
E. MAXIMUM 3/C NO. 12 AWG METAL-CLAD CABLE.
3. HILTI CP 680-M OR CP 680-P CAST-IN FIRESTOP DEVICE, CAST OR GROUTED INTO
CONCRETE FLOOR (SEE TABLE BELOW).
4. MINIMUM 1" DEPTH HILTI CP 618 FIRESTOP PUTTY STICK APPLIED AROUND CABLES
(SEE NOTES BELOW).
NOTES : 1. AS AN ALTERNATE TO HILTI CP 618 FIRESTOP PUTTY STICK, MINIMUM 2" THICKNESS
MINERAL WOOL (MINIMUM 4 PCF DENSITY) MAY BE TIGHTLY PACKED INTO FIRESTOP
DEVICE, FLUSH WITH TOP SURFACE OF DEVICE.
2. FILL MATERIAL IS OPTIONAL FOR MINIMUM 2" DIAMETER CABLE BUNDLES INSTALLED
IN 2" DEVICES, MINIMUM 2-1/2" DIAMETER CABLE BUNDLES INSTALLED IN 3" DEVICES
AND MINIMUM 3" DIAMETER CABLE BUNDLES INSTALLED IN 4" DEVICES.
3. FOR CONCRETE FLOOR OVER METAL DECKING APPLICATIONS, A METAL DECK
ADAPTER KIT IS REQUIRED.
FA
3007h
2 of 2
-
Jan. 17, 2007
UL/cUL SYSTEM NO. F-A-3007
F-RATING = 3-HR.
T-RATING = 0-HR., 1/4-HR. OR 1/2-HR.
FA3007h.011707
Tulsa, Oklahoma USA (800) 879-8000
MAXIMUM DIAMETER OF CABLE BUNDLE
PRODUCT DESCRIPTION
2"
CP 680-M 2" OR CP 680-P 2"
3"
CP 680-M 3" OR CP 680-P 3"
4-1/2"
CP 680-M 4" OR CP 680-P 4"
6-1/2"
CP 680-P 6"