Page text
Sheet
Drawing No.
HILTI, Inc.
Date
Scale
F. MAXIMUM 1/2" DIAMETER FIBER-OPTIC CABLE (24 FIBER) WITH PVC OR PE JACKET AND INSULATION.
G. MAXIMUM 20/C NO. 22 AWG SHIELDED PRINTER CABLE WITH PVC JACKET.
H. MAXIMUM 2/C NO. 18 AWG POWER OR NON-POWER LIMITED FIRE ALARM CABLE WITH OR WITHOUT
METAL JACKET (MANUFACTURED BY AFC CABLE SYSTEMS, INC.).
I. MAXIMUM 1/4" DIAMETER S-VIDEO CABLE CONSISTING OF TWO MAXIMUM 24 AWG 75 OHM COAX OR
TWISTED PAIR CABLE WITH PE INSULATION AND PVC JACKET.
3. HILTI CP 653 SPEED SLEEVE (2" OR 4") SLID INTO AND CENTERED WITHIN FLOOR OR WALL. DEVICE
FLANGES SPUN CLOCKWISE ONTO DEVICE THREADS OVER SMOKE GASKET, BUTTING TIGHTLY TO TOP
SIDE OF FLOOR, OR BOTH SIDES OF WALL (SEE NOTE NO. 4 BELOW).
4. SECURE DEVICE FLANGE TO TOP OF FLOOR WITH TWO 1-1/4" LONG CONCRETE SCREWS OR ANCHORS.
5. MINIMUM 4" THICKNESS MINERAL WOOL (MIN. 4 PCF DENSITY) TIGHTLY PACKED FLUSH WITH BOTTOM
OF FLOOR AND RECESSED FROM TOP SURFACE OF FLOOR, OR BOTH SURFACES OF WALL, TO
ACCOMMODATE FIRESTOP SEALANT.
6. NOMINAL 1-1/2" OR 2" THICK DUCT THICK DUCT WRAP (FYREWRAP DUCT OR FYREWRAP DUCT 1.5
INSULATION MANUFACTURED BY UNIFRAX, OR FIREMASTER FASTWRAP XL MANUFACTURED BY
THERMAL CERAMICS). INSULATION TO EXTEND MINIMUM 12" ABOVE FLOOR OR BOTH SURFACES OF
WALL. ENDS ARE TO BE TIGHTLY BUTTED AND TAPED. THE EXPOSED EDGES OF THE INSULATION ARE
TO BE TAPED WITH 4" WIDE PRESSURE SENSITIVE ALUMINUM FOIL TAPE.
NOTES : 1. MAXIMUM DIAMETER OF OPENING = 3" (FOR 2" DEVICE) OR 5" (FOR 4" DEVICE).
2. CABLES MAY REPRESENT 0% TO 100% VISUAL FILL OF DEVICE.
3. ANNULAR SPACE BETWEEN DEVICE AND PERIPHERY OF OPENING = MINIMUM 0".
4. AS AN OPTION IN FLOORS, STEEL SLEEVE OF DEVICE MAY BE INSTALLED FLUSH
WITH BOTTOM OF FLOOR.
5. [OPTIONAL] AS AN ALTERNATE TO SMOKE GASKET, MINIMUM 1/2" DEPTH HILTI
FS-ONE INTUMESCENT FIRESTOP SEALANT OR CP 606 FLEXIBLE FIRESTOP SEALANT
FLUSH WITH TOP OR BOTTOM SURFACE OF FLOOR, OR BOTH SURFACES OF WALL.
ADDITIONAL 1/4" BEAD OF HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT OR HILTI
CP 606 FLEXIBLE FIRESTOP SEALANT APPLIED AT POINT OF CONTACT. FIRESTOP
SEALANT IS REQUIRED ON BOTH SIDES OF A WALL.
CAJ
2 of 2
-
UL/cUL SYSTEM NO. C-AJ-3298
CABLE BUNDLE THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL ASSEMBLY
Tulsa, Oklahoma USA (800) 879-8000
F-RATING = 2-HR.
T-RATING = 2-HR.
L-RATING AT AMBIENT = LESS THAN 1 CFM (SEE TABLE)
L-RATING AT 400°F = LESS THAN 1 CFM (SEE TABLE)
3298d
Aug. 13, 2014
CAJ3298d.081314
SEALANT / GASKET
SEALANT / GASKET
MAX CABLE
FILL
CABLE TYPE
L RATING, CFM/SQ FT
L RATING, CFM
AMBIENT
400°F
AMBIENT
400°F
0%
—
1
2
LESS THAN 1LESS THAN 1
100%
ANY CABLES (ITEM NO. 2)
IN ANY COMBINATION
7
7
LESS THAN 1LESS THAN 1