2. CABLE BUNDLE TO BE A COMBINATION OF ANY OF THE FOLLOWING :
A. MAXIMUM 100 PAIR NO. 24 AWG TELEPHONE CABLE WITH PVC JACKET.
B. MAXIMUM 7/C NO. 12 AWG COPPER CONDUCTOR CONTROL CABLE WITH PVC OR XLPE JACKET AND
INSULATION.
C. MAXIMUM 4/0 AWG TYPE RHH GROUND CABLE.
D. MAXIMUM 4 PAIR NO. 22 AWG CAT 6 COMPUTER CABLE.
E. MAXIMUM RG 6/U COAXIAL CABLE.
F. MAXIMUM 1/2" DIAMETER FIBER-OPTIC CABLE (24 FIBER) WITH PVC OR PE JACKET AND INSULATION.
G. MAXIMUM 20/C NO. 22 AWG SHIELDED PRINTER CABLE WITH PVC JACKET.
H. MAXIMUM 2/C NO. 18 AWG POWER OR NON-POWER LIMITED FIRE ALARM CABLE WITH OR WITHOUT
METAL JACKET (MANUFACTURED BY AFC CABLE SYSTEMS, INC.).
I. MAXIMUM 1/4" DIAMETER S-VIDEO CABLE CONSISTING OF TWO MAXIMUM 24 AWG 75 OHM COAX OR
TWISTED PAIR CABLE WITH PE INSULATION AND PVC JACKET.
3. HILTI CP 653 SPEED SLEEVE (2" OR 4") SLID INTO AND CENTERED WITHIN FLOOR OR WALL. DEVICE
FLANGES SPUN CLOCKWISE ONTO DEVICE THREADS OVER SMOKE GASKET, BUTTING TIGHTLY TO
BOTTOM SIDE OF FLOOR, OR BOTH SIDES OF WALL.
4. SECURE DEVICE FLANGE TO BOTTOM OF FLOOR WITH TWO 1-1/4" LONG CONCRETE SCREWS OR
ANCHORS.
CAJ
2 of 2
-
UL/cUL SYSTEM NO. C-AJ-3284
Tulsa, Oklahoma USA (800) 879-8000
NOTES : 1. MAXIMUM DIAMETER OF OPENING = 3" (FOR 2" DEVICE) OR 5" (FOR 4" DEVICE).
2. CABLES MAY REPRESENT 0% TO 100% VISUAL FILL OF DEVICE.
3. ANNULAR SPACE BETWEEN DEVICE AND PERIPHERY OF OPENING = MINIMUM 0".
4. [OPTIONAL] AS AN ALTERNATE TO SMOKE GASKET MINIMUM 1/2" DEPTH HILTI FS-ONE
INTUMESCENT FIRESTOP SEALANT OR MINIMUM 1" DEPTH HILTI CP 618 FIRESTOP
PUTTY STICK FLUSH WITH BOTTOM SURFACE OF FLOOR WITH AN ADDITIONAL 1/4"
BEAD APPLIED AT POINT OF CONTACT. FIRESTOP SEALANT/PUTTY IS REQUIRED ON
BOTH SIDES OF A WALL.
CABLE BUNDLE THROUGH CONCRETE/FLOOR OR BLOCK WALL ASSEMBLY
3284d
Aug. 13, 2014
F-RATING = 3-HR.
T-RATING = 1/2-HR.
L-RATING AT AMBIENT = LESS THAN 1 CFM (SEE TABLE)
L-RATING AT 400°F = LESS THAN 1 CFM (SEE TABLE)
CAJ3284d.081314
SEALANT / PUTTY / GASKET
SEALANT / PUTTY / GASKET
MAX CABLE
FILL
CABLE TYPE
L RATING, CFM/SQ FT
L RATING, CFM
AMBIENT
400°F
AMBIENT
400°F
0%
—
1
2
LESS THAN 1LESS THAN 1
100%
ANY CABLES (ITEM NO. 2)
IN ANY COMBINATION
7
7
LESS THAN 1LESS THAN 1