Sheet
Drawing No.
HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
1 of 1
3/16" = 1"
CANADA ONLY
F-RATING = 1 1/2-HR. OR 2-HR.
FT-RATING = 0-HR., 1/4-HR., OR 2-HR.
FH AND FTH-RATINGS = 0-HR. OR 2-HR.
NOTE : TESTED WITH A 50 Pa PRESSURE DIFFERENTIAL
A
SECTION A-A
TOP VIEW
1. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR ASSEMBLY (MINIMUM 6" THICK) (2-HR.
FIRE-RATING).
2. MAXIMUM 3" NOMINAL DIAMETER PVC-XFR (SCHEDULE 40 SOLID CORE) (CLOSED OR VENTED
PIPING SYSTEM) (SEE TABLE BELOW).
3. HILTI CP 680-P [2" OR 3"] CAST-IN FIRESTOP DEVICE CAST OR GROUTED INTO CONCRETE
FLOOR (SEE TABLE BELOW).
cUL
June 18, 2013
cUL SYSTEM NO. F-B-2053
cUL FB2053a.061813
PLASTIC PIPE THROUGH CONCRETE FLOOR ASSEMBLY
TYPE OF
PENETRANT
NOM PIPE DIAM
MM (IN.)
FIRESTOP
DEVICE
F
RATING
HR
FT
RATING
HR
FH
RATING
HR
FTH
RATING
HR
PVC-XFR PIPE
38 (1-1/2)
CP 680-P 2"
2
2
2
2
PVC-XFR PIPE
51 (2)
CP 680-P 2"
1-1/2
0
0
0
PVC-XFR PIPE
76 (3)
CP 680-P 3"
1-1/2
1/4
0
0
A
1
2
3