Hilti Firestop Systems
Sheet
Drawing No.
HILTI, Inc.
Date
Scale
Saving Lives through Innovation and Education
CAJ
OUPN~
1 of 2
5/32" = 1"
Sep. 21, 2018
UL/cUL SYSTEM NO. C-AJ-2831
F-RATING = 2-HR.
T-RATING = 0-HR OR 2-HR. (SEE NOTE NO. 4 BELOW)
FT-RATING = 0-HR OR 2-HR. (SEE NOTE NO. 4 BELOW)
FH-RATING = 2-HR.
FTH-RATING = 0-HR OR 2-HR. (SEE NOTE NO. 4 BELOW)
L-RATING AT AMBIENT = LESS THAN 1 CFM / SQ FT
L-RATING AT 400°F = LESS THAN 1 CFM / SQ FT
NOTE : THIS SYSTEM TESTED TO 50 PA PRESSURE DIFFERENTIAL
CAJ2831a.092118
PLASTIC PIPE THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL ASSEMBLY
A
A
SECTION A-A
BOTTOM VIEW
Plano, Texas USA (800) 879-8000
1
3
4
5
6
7
8