HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
cUL
2 of 2
-
Sep. 20, 2013
cUL SYSTEM NO. C-AJ-2678
cUL CAJ2678a.092013
PLASTIC PIPE THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL ASSEMBLY
CANADA ONLY
F-RATING = 2-HR.
FT-RATING = 2-HR.
FH-RATING = 2-HR.
FTH-RATING = 2-HR.
L-RATING AT AMBIENT = LESS THAN 1 CFM / SQ FT
L-RATING AT 400°F = LESS THAN 1 CFM / SQ FT
NOTE : TESTED WITH A 50 Pa PRESSURE DIFFERENTIAL
NOTES : 1. MAXIMUM DIAMETER OF OPENING = 5".
2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 1/2".
3. HILTI CP 648E WRAP STRIP WITH RETAINING COLLAR, AND HILTI FS-ONE
INTUMESCENT FIRESTOP SEALANT ARE REQUIRED ON BOTH SIDES OF A WALL.
1. CONCRETE FLOOR OR WALL ASSEMBLY (2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR OR WALL (MINIMUM 4-1/2" THICK).
B. ANY UL/cUL CLASSIFIED PRECAST (HOLLOW-CORE) CONCRETE FLOOR (MINIMUM 6" THICK).
C. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
2. MAXIMUM 4" NOMINAL DIAMETER XFR 15/50 PVC PLASTIC PIPE (SCHEDULE 40) (SOLID CORE) (CLOSED
OR VENTED PIPING SYSTEM).
3. MINIMUM 1" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT FLUSH WITH BOTTOM SURFACE OF
FLOOR OR BOTH SIDES OF A WALL.
4. HILTI CP 648E WRAP STRIP (NOMINAL 3/16" THICK x 1-3/4" WIDE) CONTINUOUSLY WRAPPED AROUND
THE OUTER CIRCUMFERENCE OF THE PIPE, AS SPECIFIED IN THE TABLE BELOW, WITH ENDS BUTTED
AND HELD IN PLACE WITH TAPE. WRAP STRIP TO BE BUTTED TIGHTLY AGAINST BOTTOM SURFACE OF
FLOOR.
5. HILTI 1-3/4" RETAINING COLLAR WRAPPED OVER THE WRAP STRIPS, OVERLAPPING MINIMUM 1".
6. NOMINAL 1/2" WIDE STAINLESS STEEL HOSE CLAMP SECURED TO THE COLLAR AT ITS MID-HEIGHT.
7. EVERY OTHER TAB OF RETAINING COLLAR SECURED TO BOTTOM OF FLOOR WITH 1/4" x 1-3/4" LONG
STEEL EXPANSION BOLTS, 3/16" x 1-1/4" LONG STEEL CONCRETE SCREW ANCHORS, OR 0.145"
DIAMETER x 1-1/4" LONG POWDER ACTUATED FASTENERS IN CONJUNCTION WITH 1/16" THICK STEEL
WASHERS (EX. HILTI KWIK-BOLT 3, KWIK-CON II+, OR X-U PINS).
MAX PIPE SIZE
NUMBER OF LAYERS
OF CP 648E 1-3/4"
3"
2
4"
3