HILTI, Inc.
Tulsa, Oklahoma USA (800) 879-8000
Date
Scale
1. CONCRETE FLOOR OR WALL ASSEMBLY (2-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR (MINIMUM 4-1/2" THICK).
B. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL (MINIMUM 5" THICK).
C. PRECAST (HOLLOW-CORE) CONCRETE FLOOR (MINIMUM 6" THICK).
D. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
2. PENETRATING ITEM TO BE ONE OF THE FOLLOWING :
A. MAXIMUM 2" NOMINAL DIAMETER POLYPROPYLENE (PP) PLASTIC PIPE (SCHEDULE 80) (CLOSED OR
VENTED PIPING SYSTEM).
B. MAXIMUM 2" NOMINAL DIAMETER AQUARISE CPVC PLASTIC PIPE (SDR 11) MANUFACTURED BY IPEX,
INC. (CLOSED PIPING SYSTEM ONLY).
3. NOMINAL 1" THICK AB/PVC PIPE INSULATION.
4. MINIMUM 4" THICKNESS MINERAL WOOL (MIN. 4 PCF DENSITY) TIGHTLY PACKED, RECESSED FROM
BOTTOM OF FLOOR.
5. MINIMUM 1/2" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT.
6. HILTI CP 648E WRAP STRIP (NOMINAL 3/16" THICK x 1-3/4" WIDE) CONTINUOUSLY WRAPPED AROUND
THE OUTER CIRCUMFERENCE OF THE PIPE, COVERING TWO TIMES, WITH ENDS BUTTED AND HELD IN
PLACE WITH TAPE. WRAP STRIP TO BE BUTTED TIGHTLY AGAINST BOTTOM SURFACE OF FLOOR.
7. HILTI 1-3/4" RETAINING COLLAR WRAPPED OVER THE WRAP STRIPS, OVERLAPPING MINIMUM 1".
8. HILTI COLLAR CLAMP FASTENED AT MID-HEIGHT OF RETAINING COLLAR.
9. EVERY OTHER TAB OF RETAINING COLLAR SECURED TO BOTTOM OF FLOOR WITH 1/4" x 1-3/4" LONG
STEEL EXPANSION BOLTS, 3/16" x 1-1/4" LONG STEEL CONCRETE SCREW ANCHORS OR 0.145 DIAMETER
x 1-1/4" LONG POWDER ACTUATED FASTENERS IN CONJUNCTION WITH WITH 15mm DIAMETER STEEL
WASHERS (EX. HILTI KWIK-BOLT 3, KWIK-CON OR DX PINS).
NOTES : 1. MAXIMUM DIAMETER OF OPENING = 5".
2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 5/8".
3. HILTI CP 648E WRAP STRIP WITH RETAINING COLLAR, AND HILTI FS-ONE INTUMESCENT
FIRESTOP SEALANT ARE REQUIRED ON BOTH SIDES OF A WALL.
cUL
2 of 2
-
Sep. 28, 2006
cUL SYSTEM NO. C-AJ-2055
cUL CAJ2055b.092806
CANADA ONLY
F AND FT-RATINGS = 2-HR.
FH AND FTH-RATINGS = 0-HR.
NOTE : TESTED WITH A 50 Pa PRESSURE DIFFERENTIAL