1. CONCRETE FLOOR OR WALL ASSEMBLY (3-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR OR WALL (MINIMUM 4-1/2" THICK).
B. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
2. [OPTIONAL] MAXIMUM 8" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 40 OR HEAVIER).
3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING (ALSO SEE NOTE NO. 3 BELOW) :
A. MAXIMUM 6" NOMINAL DIAMETER PVC PLASTIC PIPE (CELLULAR OR SOLID CORE).
B. MAXIMUM 6" NOMINAL DIAMETER ABS PLASTIC PIPE (CELLULAR OR SOLID CORE).
C. MAXIMUM 6" NOMINAL DIAMETER FRPP PLASTIC PIPE.
D. MAXIMUM 6" NOMINAL DIAMETER CPVC PLASTIC PIPE.
E. MAXIMUM 6" NOMINAL DIAMETER XFR 15/50 PVC PLASTIC PIPE (SOLID CORE).
cUL
1 of 2
5/32" = 1"
Aug. 28, 2013
cUL SYSTEM NO. C-AJ-2053
cUL CAJ2053b.082813
PLASTIC PIPE THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL ASSEMBLY
CANADA ONLY
A
A
SECTION A-A
BOTTOM VIEW
L-RATING AT AMBIENT = LESS THAN 1 CFM / SQ FT
L-RATING AT 400°F = LESS THAN 1 CFM / SQ FT
W-RATING = CLASS I (SEE NOTES NO. 6 AND 7 BELOW)
NOTE : TESTED WITH A 50 Pa PRESSURE DIFFERENTIAL
F-RATING = 3-HR.
FT-RATING = 0-HR. OR 2-HR.
FH-RATING = 0-HR. OR 3-HR.
FTH-RATING = 0-HR. OR 2-HR.